Loading...
HomeMy WebLinkAboutALL DOCS - 14-00063 - 311 S Center St - BYUI David O. McKay - Fan & Chiller UpgradesCommunity Development Department Phone (208)359-3020 Inspection Hotline: (208)372-2344 INSPECTION REPORT Inspection Type Building Type Inspection ELECTRICAL BLD-ELEC ELE-FINAL Permit Number: Address: 311 South Center Street Project: 14-00063 BYU-I David O. McKay - Chiller & Fan Upgrades Inspection Date 8/26/2014 Inspection Result: PASS D ESCRIPTIO N CO MMEN TS STATUS Receptacles have correct polarity, grounding, no open neutrals, etc. 200.10(B) COMPLETED Check for continuity and completeness in metal raceways and enclosures. 300.10 COMPLETED Check boxes and conduit bodies for adequate space for conductors.314.16 COMPLETED Check for closure of unused openings.314.17(A)COMPLETED Verify that boxes in walls and ceilings are flush with the finished surface or, if surfaces are noncombustible, within 1/4 in. of the finished surface.314.20 COMPLETED Check for excessive gaps between edges of boxes and plaster, plasterboard, or drywall surfaces.314.21 COMPLETED Check for covers on boxes.314.25, 314.28(C)COMPLETED Check that receptacles project from metal faceplates or are flush with nonmetallic faceplates and that the faceplates cover openings.406.4(D) COMPLETED Check receptacles for proper polarity and for grounding and bonding connections. 406.3, 250.146, 200.11 COMPLETED Approved for a final and C.O.In NE corner of building in remodeled area for two offices. COMPLETED Page 1 of 2 Inspector: Bret Stoddard Page 2 of 2