HomeMy WebLinkAboutREVIEW ACTION - 08-00450 - Ferrin Square -Mini Golf Review ActionclTY (]]:
s'pxxlBs
Ame\itt\ tlani4' deflfru4tl
P.O Box 280
19 E. Main St.
Rexburg, ldaho 83440
Phone (208) 359-3020
Fax (208) 359-3022Review Action
AccessibilitY Review
Exiting Review
Plumbing Sewer Drain Review
October 1, 2008
Permit Number: 08 00450
project Name: Ferrin Square Miniature Golf Remodel
Project Type: Commercial Remodel
Review ltem Actions Required for Approval
Plumbing Potable Water Review
#1#
No electrical plan was submitted- make sure
that this is wired to the 2008 NEC'
Restrooms meet code requirements'
Meets code requirements.
All plumbing drains are required to be installed
according to tfre Uniform Plumbing Code 2003
edition. All drains are required to be inspected
and tested before covering.
Commercial kitchen drains are required to have
a grease traP or intercePtor'
Allwater lines are required to be tested and
inspected before covering. Water lines are
required to be sized large enough to provide
water requirements for all added fixtures
according to the Uniform Plumbing Code 2003
edition.
Parcel#'s RPRRXB1038158O
Approved
0912412008
09/30/2008
09/30/2008
1010112008
1010112008
ClTY $F
Rsx*vRG
Aneik\ Itafl ii (kt ft nu t iq,
P.O Box 280
19 E lMain St.
Rexburg, ldaho 83440
Fhone (208) 359-3020
Fax (208) 359-3022Review Action
October 1,2008
Permit Number: 08 00450
Project Name: Ferrin square Miniature Golf Remodel
Project Type: Commercial Remodel
Review ltem Approvedhi
Required Fire Flow
Water Supply
Fire Access Roads
Fire Extinguishers
Automatic Fire Extinguishing Systems
Standpipes
Commercial Cooking
Alarm Systems
Parcel#'s RPRRXBl038l580
Fire protection system is required to providecoverage according to the lnternational firecode 2006 edition.
Wa-ter supply for this occupancy may not be 1O!O1/2OOBsufficent. The flre sprinkler system ii suppliedwith a 2" line. This is sufficent for a residentialsprinkler system only.
Established. 1Arc1nOOB
Fire extinguishers are not shown on prans. Ail lorolr2oogfire extinguisher are required to be installed
according to the International Fire Code 2006edition prior to final fire inspection.
Automatic fire sprinkler system is required to be lololl2oo}upgraded to meet the requirements foroccupancy.
N/A
10t01t2008
10t01t2008
when commerciar cooking area is added to the loroir2oogoccupancy it must be reviewed and approvedbefore installing any equipment.
The fire alarm system is required to be upgrade lorolr2oo}to provided coverage specified in theInternational Fire Code 2006 edition.