Loading...
HomeMy WebLinkAboutREVIEW ACTION - 08-00450 - Ferrin Square -Mini Golf Review ActionclTY (]]: s'pxxlBs Ame\itt\ tlani4' deflfru4tl P.O Box 280 19 E. Main St. Rexburg, ldaho 83440 Phone (208) 359-3020 Fax (208) 359-3022Review Action AccessibilitY Review Exiting Review Plumbing Sewer Drain Review October 1, 2008 Permit Number: 08 00450 project Name: Ferrin Square Miniature Golf Remodel Project Type: Commercial Remodel Review ltem Actions Required for Approval Plumbing Potable Water Review #1# No electrical plan was submitted- make sure that this is wired to the 2008 NEC' Restrooms meet code requirements' Meets code requirements. All plumbing drains are required to be installed according to tfre Uniform Plumbing Code 2003 edition. All drains are required to be inspected and tested before covering. Commercial kitchen drains are required to have a grease traP or intercePtor' Allwater lines are required to be tested and inspected before covering. Water lines are required to be sized large enough to provide water requirements for all added fixtures according to the Uniform Plumbing Code 2003 edition. Parcel#'s RPRRXB1038158O Approved 0912412008 09/30/2008 09/30/2008 1010112008 1010112008 ClTY $F Rsx*vRG Aneik\ Itafl ii (kt ft nu t iq, P.O Box 280 19 E lMain St. Rexburg, ldaho 83440 Fhone (208) 359-3020 Fax (208) 359-3022Review Action October 1,2008 Permit Number: 08 00450 Project Name: Ferrin square Miniature Golf Remodel Project Type: Commercial Remodel Review ltem Approvedhi Required Fire Flow Water Supply Fire Access Roads Fire Extinguishers Automatic Fire Extinguishing Systems Standpipes Commercial Cooking Alarm Systems Parcel#'s RPRRXBl038l580 Fire protection system is required to providecoverage according to the lnternational firecode 2006 edition. Wa-ter supply for this occupancy may not be 1O!O1/2OOBsufficent. The flre sprinkler system ii suppliedwith a 2" line. This is sufficent for a residentialsprinkler system only. Established. 1Arc1nOOB Fire extinguishers are not shown on prans. Ail lorolr2oogfire extinguisher are required to be installed according to the International Fire Code 2006edition prior to final fire inspection. Automatic fire sprinkler system is required to be lololl2oo}upgraded to meet the requirements foroccupancy. N/A 10t01t2008 10t01t2008 when commerciar cooking area is added to the loroir2oogoccupancy it must be reviewed and approvedbefore installing any equipment. The fire alarm system is required to be upgrade lorolr2oo}to provided coverage specified in theInternational Fire Code 2006 edition.