Fax (208) 3s9-3022Review Action
January 29,2008
Permit Number: 08 00017
Project Name: Fireplace by Design Remodel
Project Type: Commercial Remodel
Review ltem
Approved
Development Standards Review Elevated concrete and and fencing atong MainStreet must be removed as it is in-tne publicright-of-way and for vehicles exiting the site,these obstructions pose a sight dislancehazard to pedestrians and bicyclists along theside walk.
Parking plan as submitted does not followparking configuration that is ,,grandfathered in,,nor does it meet curent code. Specificially thenew proposaldoes not allow adequate aislewidthsfor 90 degree parking. lt appears that the"grandfathered" parking configuration includedonly angled parking with ingress from 2nd Eastand egress to Main Street.
Parcel #'s RPRRXBl04OO22O
?n;E({/^4
us){(,
-^1*/4
apL-
t oa-
doL.^>
7e 7e-3o[ts--
uea #- \d;L[- ,EL":I Ktf
*2..€/ /r/f A-*.reJ
- rL;= rta-tor
Er #a',-c
fPg- u.l( t; or4.- t^:;+'{^- ?ryu;ry'
A--/Zo;:;- Tt-> P.z-=/,t-g-- f,L=
(*n tNL+o +rt-- K6A qsfr,:
Le/- -/o B;*q fu$;-e {aZS '
fle-az- re C-reA FossrJ/s-
{ a--ro
CI'I'Y OF
REXBURG
c!' ----
AnEr i ca\ Fqni l,' Cnmtnuli ll
P.O Box 280
19 E tilain St.
Rexburg, Haho 832140
Fhone (208) 359-3020
Fax (208) 359-3022Review Action
January 30, 2008
Permit Number: 08 00017
Project Name: Fireplace by Design Remodel
Project Type: Commercial Remodel
Review ltem
i::l$irltffiffi
Electrical Circuits Review
Electrical Service Review
Electrical Energy Lighting Compliance Review
Water and Sewer Service
Plumbing Sewer Drain Review
Plumbing Storm Drain Review
Plumbing Potable Water Review
Actions Required for Approval Approved
Accessibility Review
Exiting Review
Building Code Fire Compliance Review
Parcel#'s RPRRXBIO4OO22O
No electrical plans were submitted for the
circuits, make sure that everything meets the
2005 NEC that is changed or added.
The service is not changing, if it does change at
all, make sure that it meets the 2005 NEC.
The lighting is not changing from what it was,
so no lighting energy compliance is required.
Approved
All drainage line that are add to the existing
plumbing are required to be tested and
inspected.
Not required according to plans submitted.
Allwater lines are required to be protected from
health hazards. lf any backflow devices are
installed they are required to be tested before
final inspection.
Plans appear to have an accessible restroom.
Get with Jon Berry during construction to make
sure.
Meets code requirements.
Provide one hour firewall and rated doors
between occupancies.
01/09/2008
01t09t2008
01/09/2008
01t14t2008
01t14t2008
01t14t2008
01t14t2008
01t't4t2008
01t14t2008
01t14t2008
clt-Y oF
REXBURG
Anrericu\ Farnih Cn mn utri ly
PO Box 280
19 E. Main St.
Rexburg, ldaho 83440
Fhone (208) 359-3020
Fax (208) 359-3022Review Action
January 30, 2008
Permit Number: 08 00017
Project Name: Fireplace by
Project Type: Commercial
Review ltem
Design Remodel
Remodel
Actions Required for Approval Approved
Fffi llrlllllggr\iltrlliN Il
Required Fire Flow
Water Supply
Fire Access Roads
Fire Extinguishers
Automatic Fire Extinguishing Systems
Standpipes
Commercial Cooking
Alarm Systems
Established
Established
Established
Fire extinguishers are required to be installed.
2A1 OBC extinguishers are required.
Not required for this occupancy.
Not required for this occupancy.
Not required for this occupancy.
Not required for this occupancy.
01t14t2008
01t't4t2008
01t14t2008
01t14t2008
01t14t2008
01t14t2008
01t14t2008
01t14t2008
Parcel#'s RPRRXBIO4OO22O