Fax (208) 3s9-3022Review Action
November 9,2007
Permit Number: 07 00405
Project Name: Gymnastics Center-Site plan
Project Type: Site Plan Review
Review ltem
Plumbing Review
Parking Configuration ldentify handicapped aisle at spaces.
Miscellaneous Provide accessibte pedestrian access to thepublic right-of-way without using the driveways.
Provide grading plan and drainage details.
Parcel #'s RPRAIRCP020060
Approved
11t09t2007
11t09t2007
cllY oIj'REXBURG
c\t - ----
Aircr ia\ Farnil)' Commuti ty
P.O Box 280
19 E lilain St.
Rexburg, Haho 83440
Phone (208) 359-3020
Fax (208) 359-3022Review Action
November 9,2007
Permit Number: 07 00405
Project Name: Gymnastics Center-Site Plan
Project Type: Site Plan Review
Review ltem Actions Reouired for Aooroval
ilffi$iffiiffi il]i]i,tlffi*
Additional Comments
Parcel#'s RPRAIRCP020060
Approved
11t09t2007
CII-Y OF-REXBURG
c\t ----.-'-
Anter ica\ Fanily Co mtnuti ly
P.O Box 280
19 E Main St.
Rexburg, Haho 83440
Fhone (208) 359-3020
Fax (208) 359-3022Review Action
November 9,2007
Permit Number: 07 00405
Project Name: Gymnastics Center-Site plan
Project Type: Site Plan Review
Review ltem
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved
-1 *'
One-way driving isle must be clearly marked asone-way.
Garbage container location is not shown on thesite plan. This must be fully screened from theright-of-way and may not be located within 20feet of the right-of-way or any pedestrian
walkway.
Internal pedestrian walkway must connect tothe crosswalk along the right-of-way.
One handicap stall must be van accessible.
A 6 foot landscape strip is required between thesidewalk and the building facade.
The landscape strip shown on the site planrevision dated 101312001averages as at least 6feet wide.
Southwest parking stall needs a 6x22 foot
backing area.
The ordinance does not specifically state theparking requirement for a private gymnastics
center. In researching other City's standardsand reading minutes from meetings of othercities, the following requirement was
determined:
1 -space per 500 sq. ft. of gross floor area (non_
office area.)
3 spaces per 1000 sq. ft. for areas designatedfor office use.
This totals 25 spaces for this project.
2 parking stalls in the Southeast corner of thelot are located in the 10 foot front yard setback.
Parking must be visually buffered from the right_of-way with landscaping. Also an 1g foot widelandscaped berm is required along Highway 20.Please submit a detailed lanOscaping plan forreview.
09t14t2007
10t04t2007
't0t04t2007
10t04t2007
10t04t2007
10t04t2007
10t04t2007
10t04t2007
10t05t2007
Approved Site Plan
ilExnciic(\' '.-'-*---..
Ameriil\ thni[ (hmmwiry
P.O Box 280
19 E tilain St.
Rexburg, ldaho 83440
Fhone (208) 359-3020
Fax (208) 359-3022Review Action
November 9,2007
Permit Number:
Project Name:
Project Type:
Review ltem
07 00405
Gymnastics Center-Site Plan
Site Plan Review
Actions Reouired for Aooroval
A detailed landscaping plan is still needed for
review. Landscaping of the 18 foot wide berm
along Highway 20 must follow the approved
cross section as shown in the Light Industrial
design standards.
Please submit a lighting plan for review -
inluding photometric layout information.
Approved
Approved Site Plan
Parcel #'s RPRAIRCP02OO6O
c I'l-Y o f
RExgURC
c\'t -"'''-
An r e r i c a\ f atnily C o mn un i ty
P.O Box 280
'19 E lMain St.
Rexburg, ldaho 83440
Fhone (208) 359-3020
Fax (208) 359-3022Review Action
November 9,2007
Permit Number: 07 00405
Project Name: Gymnastics Center-Site Plan
Project Type: Site Plan Review
Access to Hydrants
Vicinity Map Provided
Fire Lane Signage
Existing Hydrants
Fire Apparatus Access
Required Fire Flow
Proposed Hydrants
Fire Sprinkler System Required
Actions Reouired for Anoroval
VIA PUBLIC STREETS
VICINITY MAP SHOWS "CEDAR FALLS
LOOP", STREET IS ACTUALLY JET STREAM
DRIVE.
NOT REQUIRED
ONE EXISTING HYDRANT SHOWN
(APPROXTMATELY 140 FEET TO
STRUCTURE), SECOND HYDRANT (NOT
sHow) ts APPRoxtMATELY 235 FEET TO
STRUCTURE.
ACCESS ON EAST SIDE OF BUILDING
SHOWS WIDTH TO BE 16 FEET,20 FEET IS
THE MINIMUM REQUIREMENT FOR FIRE
APPARATUS.
CoRRECTED 10t5t07
UNKNOWN FIRE FLOW, UNKOWN TYPE OF
CONSTRUCTION, FI RE SUPPRESSION
SYSTEM, ETC.
UNKNOWN AS OF 10106107
REQUIRED FIRE FLOW FOR 9165 SQUARE
FOOT STRUCTURE IS 2OOO SQUARE
FEET/TWO HOURS FROM A MINIMUM OF
TWO HYDRANTS WITHIN 450 FEET.
SQUARE FOOTAGE MAY DICTATE
INCREASED FIRE HYDRANTS, PLEASE
PROVIDE MORE INFORMATION
EXISTING HYDRANTS PROVIDED.
PLEASE PROVIDE MORE INFORMATION
(SQUARE FOOTAGE, OCCUPANCY LOAD,
ETC.) FOR DETERMT NAT|ON.
NO ADDITIONAL INFORMATION PROVIDED
AS OF 10t06t07
NOT REQUIRED
Approved
08t28t2007
08t28t2007
08t28t2007
08t28t2007
10t06t2007
10t09t2007
10t09t2007
't0t09t2007
Review ltem
cll'Y 0F
a_ _-- -_
REXBURG
C\, -----
Am.rtrc's FafiiU Ca mnw i lY
P.O Box 280
19 E lvlain St.
Rexburg, Haho 83440
Phone (208) 359-3020
Fax (208) 359-3022Review Action
November 9,2007
Permit Number: 07 00405
Project Name: Gymnastics Center-Site Plan
Project Type: Site Plan Review
Review ltem
Approved Site Plan
Parcel#'s RPRAIRCPO2OO6O
Actions Required for Approval Approved
1. No facilities are show for the management of
stormwater.
2. No lighting plans are included.
3. No method is shown for sanitation facilities
location.
Items addressed. The location for the
sanitation dumpster is very difficult to get to.
We willwork with them during construction for
a better location.
cl1'Y or
REXB
Am er i c s,\ F dil ily Ca m, n u t t i ty
P.O Box 280
19 E lrain St.
Rexburg, ldaho 83440
Fhone (208) 359-3020
Fax (208) 359-3022Review Action
November 9,2007
Permit Number: 07 00405
Project Name: Gymnastics Center-Site plan
Project Type: Site Plan Review
Review ltem Actions Required for Aooroval
NO HYDRANT FLOWS PROVIDED.
NO HYDRANT FLOWS PROVIDED AS OF
10t06t07
Approved
Hydrant Flows Provided
Parcel #'s RPRAIRCPO2OO6O
CITY OF
REXBURG
c\' '-*-'- *^-
An rc r i e\ Filarni ly Cn ilm u t t i ly
P.O Box 280
19 E lilain St.
Rexburg, Haho 83440
Phone (208) 359-3020
Fax (208) 359-3022Review Action
November 9,2007
Permit Number: 07 00406
Project Name: Gymnastics Center
Project Type: Commercial New
Review ltem Actions Reouired for Anoroval
iffil,ffiiilllliiili
Electrical Circuits Review
Water and Sewer Service
Plumbing Sewer Drain Review
Plumbing Storm Drain Review
Plumbing Potable Water Review
Accessibility Review
Building Type Compliance
Electrical Energy Lighting Compliance Review
Electrical Service Review
Exiting Review
Height and Area Review
Energy Conservation Compliance Review
Building Code Fire Compliance Review
No electrical plan was submitted, make sure
that everything electrical is installed to the 2005
NEC code.
N/A
All drains are required to be tested and
inspected before covering.
N/A
Allwater lines are required to be tested and
inspected before covering.
Meets code requirements.
Building has been reviewed as Type VB. The
occupancy is A-3.
No electrical plan was submitted, need to see a
power riser diagram. The service is going to be
a2O0 ampere service, make sure that this is
wired to the 2005 NEG.
Maximum occupancy # must be posted.
ldentify exit signs and emergency lighting.
Panic hardware is required on the doors of A
occupancies with an occupant load greater
than 100. Provide stairdetails. ldentify
gaurdrails at mezzanine.
As per IBC Table 503, building requires a
sprinkler system in order to be a two story
structure. Also as per Table 503, the area of
the building is required to be a maximum of
10500 sq. ft.
Provide energy review for mechanical, electrical
and envelope.
Provide fire-blocking detail at mezzanine.
Approved
09t05t2007
09t07t2007
09t07t2007
09t07t2007
09t07t2007
ogt14t2007
09t14t2007
10t22t2007
11t08t2007
11t09t2007
11t09t2007
11t09t2007
11t09t2007
CITY OF
REXBURG
Ameriu\ Farnily Co mmuni tv
P.O Box 280
19 E Main St.
Rexburg, ldaho 83440
Fhone (208) 359-3020
Fax (208) 359-s022Review Action
November 9,2007
Permit Number: 07 00406
Project Name: Gymnastics Center
Project Type: Commercial New
Review ltem
Mechanical Review
Structural Review
Waste Water Application
Waste Water Grease Trap Form
Miscellaneous
Parcel #'s RPRAIRCPO2OO6O
Provide mechanical details and sizing.
Provide structural documents for wood building,foundation of the wood building and themezzanine. The steel building plans do notidentify another structure or a mezzanine beingattached. The steel building plans identity a -
31.5 lb/sq.ft. snow load. The minimum snowload for the City of Rexburg is 35 tb./sq. ft.Special inspections are required for structuralfill, concrete foundation, high strength boltingand any welding. please provide the name ofthe firm that will be performing the specialinspections. Provide truss details for the woodtrusses prior to frame inspection. All footingsmust be 36" below grade for frost.
Approved
11t09t2007
11t09t2007
ldentify masonry flashing and waterproof barrieron plans.
CITY Of
REXBURG
c\'' - _- --'
Ameriu\ Ihnily Commwi ty
P.O Box 280
19 E lilain St.
Rexburg, Haho 83440
Fhone (208) 359-3020
Fax (208) 359-3022Review Action
November 9,2007
Permit Number: 07 00406
Project Name: Gymnastics
Project Type: Commercial
Center
New
Review ltem
Approved
Required Fire Flow See site ptan Review OglOTl2OOT
Water Supply See site plan Review OglOTl2OOT
Fire Access Roads See site plan Review ogtOTl2OoT
Fire Extinguishers Fire extinguishers are to be instalted prior to ogtoTt2oolfinalfire inspection.Automatic Fire Extinguishing systems Not required for this occupancy according to ogloTl2ooTplans provided.
standpipes N/A ogrcTnooT
commercialcooking N/A ogrcTnoo1
Alarm systems Not required according to plans provided. oglo?t2ooT
Parcel #'s RPRAIRCP020060
hEXBuRG
c\' *_"'-- ---
Anteriu\ Fhmib' Commwi ty
P.O Box 280
19 E lilain St.
Rexburg, Haho 83440
Fhone (208) 3S9-3020
Fax (208) 359-3022Review Action
November 9,2007
Permit Number: 07 00406
Project Name: Gymnastics Center
Project Type: Commercial New
Development Standards Review
Parcel #'s RPRAIRCPO2OO6O
As part of the transitional design standards forthe Highway 20 corridor, a minimum 1g footwide landscaped berm is required between therear elevation and the right-of-way for Highway20. Landscaping must follow the cross sectionshown in the Light lndustrialdesign standards.
The office area on the front elevation of thebuilding must incorporate one repeating
element of color, texture, or material modulechange every 30 feet horizontally. Thisrequirement is met vertically, but nothorizontally.
Approved
't0t18t2007
11t01t2007
Review ltem
Development Standards Review