Fax (208) 359-3022Review Action
June 8,2006
Permit Number:
Project Name:
Project Type:
Review ltem
Exiting Review
Building Code Fire Compliance Review
StructuralReview
Mechanical Review
lnterior Environment
Water and Sewer Service
Plumbing Potable Water Review
Plumbing Sewer Drain Review
Parcel#'s RPRRXB10381611
06 00253
Mom's Kandy Kitchen-Remodel
Commercial Remodel
Actions Required for Approvat Approved
A 9" ramp at the entrance is identified. This
ramp must meet the requirements of the
Chapter 11 of the 2003 International Buyilding
Code (lBC) and ICC/ANSI A117'1. In the
restroom, there mujst be a 30"x48" wheelchair
space that is not in the swing of the door'
Meets code requirements.
The basement is not identified. There must be
a one-hour fire seperation from the basement to
the upper floor.
Structural members in the basement must be
connected with brackets. Get with Jon Berry
(our Commercial Inspectorfor) for a
walkthrough prior to construction.
lf any changes are made to HVAC, a
mechanical permit is required.
All new services are required to be tested and
inspected before covering.
Allwater piping is required to be tested and
inspected before covering.
Grease trap required for thus occupancy.
06/08/2006
06/08/2006
06/08/2006
06/08/2006
06/08/2006
REXBURG--'.------ Cr{i, *-------__
Aruede's llawily t)a fr r ildty
P.O Box 280
19 E l\4ain St.
Rexburg, ldaho 83440
Fhone (208) 359-3020
Fax (208) 359-3022Review Action
June 8, 2006
Permit Number: 06 00253
Project Name: Mom's Kandy Kitchen-Remodel
Project Type: Commercial Remodel
Review ltem
Parcel#'s
Occupancy requires fi re extinguishers.
Approved
"'ffi.<:
RPRRXB1038l611