reviewed the drawings for the Parkside Clubhouse and have identified the following
A new site plan was not provided with the drawing. Provide handicapped parking
and identiffthe accessibfi route fromthe buiiding to the handicapped spaces and
to the pedistrian walks. Id.entify dinrensions from the building to tlre other
buildings and to the ProPerlY line.
The plans must be stamped ty a Hcensed professional as per the 2000 International
Building Code (IBC) Section 106.1. Provide structural calculations.
submit manufaeturer's certificate of compliance for alt components as per IBC
Section 16)13.5.
Provide 1 1r. separation between the pool eqlripment loofir and the rest of the
building. Identify the door to this room as a fire rated door'
Identify exit signs.
Please provide truss details before framing inspection'
Energycalculations are required as per the 2000 International Energy
Conservation Code.
The energy code conopliance documents that,vou provided me for the Rexburg,
Idaho parkside Clubhouse are for Spanish Fork Utah and were created using an
outdated software. Please provide a new checklist using COM Check (available at
energycodes.com). Be sure to pick the 2000 IECC and Rexburg, Idaho &om the
drop down lists.
9. I have attached a copy ofthe Fire Department review to the back ofthis
document. Please resolve any issues identified by tlen
please provide me with 2 new copies of corrected plans. If you have any questions, please
eive me a calT at 359-3020 ext. 324.
Val Christensen
Buildins Official
2.
aJ.
4.
5.
6.
4t"
8.
e;nv ,/ m,o6*ny
STATE OF IDAHO
P0. Box 280
1 2 North Center Street
Rexburg, ldaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@srv.net
REXB ITRG-MAD I S O]Y C O UI{TY
EMERGEIVCY StrRWCES
26 NORTII CENTER STKEET
REXBT]RG, IDAHO 83440
208-3s9-3010
208-3s9-3006 tAx
2000 International Fire Code
Plan Review
Building Nanee: GEORGETOWN Cr'T-IBHOUSE
Buildins Address: IINKNOWN
Plan Date: UNKNOWN
Review Date: 10-5-03
Stories: ONE Type of Construction: V-B
Occupanci; Classifi cation: A-3 Existing Floor A-rea: N1A
l.{ew Consiruciion Floor Aiea: APPROXIMATELY 4,500 SQU'{RE FEnT
I Required Fire Flow (Appendix B). 1750 GPII/TWO HOURS
COMMENTS: FIRE FI-OW i\iAY BE REDUCED IF STRUCTURE HAS AN
APPROVED AUTOMATIC FIRE SUPPRESSION SYSTEM INSTAILED'
2. Water Suppiy (Section 508, Appendix C) Required: YES
fire Hydrant Location: TWO PROPOSED HYDRANTS
fire Hydrant Flows: UNKNOWN
Fire Flow Test Location: N/A
Fire Flow Supplied By: N/A
Other Approved Water Source: NONE
Water Supply Acceptable: NO
Fire Hydrant Location Acceptable: NO
water Supply comments: uNr(NowN HTDRANT FLow, PLEASE pRowDE
ENGINEERS CALCULATION FOR FLOWS. UNCLEAR OF'HTDRANT
LOCATIONS, PLEASE PROyIDE IMPRO\rED SITE PLAN.
3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: yES
Acceptable Width: NO Length: NO Sur ce: OK
Complete Road Acceptable: NO
comments: No srrE PLAN TNCLUDED wrrH BUTLDTNG pLANs.
4. Access Roads and Water Supply, including fire hydrants are required to be installed
and made serviceable priorto and during time of construction (Section 501):
comments: rF Nor TNSTALLED PRroR To CONSTRUCTTON AND MADE
OPERATIONAI., A STOP WORK ORJER WILL BE ISSLIED.
5. Installation of portable fire extinguishers (Section 906) Required: yES
Location shown: NOT SHOWN Type provided acceptable: NOT SHOWN
COTNMENtS: NEED TO PROVIDE MINIMUM OF 2A1OBC EXTINGLqSHI,R nri
KITCHT"N AREA, AT LEAST TWO OTHERS IN BUILDING WITHIN TRAVEL
DISTANCES.
6. Automatic fire extinguishing systems (Section 903) Required: NO
Type of system being instailed: NOT SHOWN
Sprinkler system monitoring (Section 907) required:
Comments: NONE
7. Standpipes (Section 905) required: NO
Type required: Comments:
8. ventiiating hood and duct fire extinguisher system (section 609) required: No
Type being provided:
Automatic fuel shut-off required:
Portable fue extinguisher shown:
Comments:
9. Fire alarm systems (Section 907) required: yES
Type of system required: Manuai: Automatic: X
Type of system being provided: Manual: Automatic:
Components of system shown: Smoke Detectors:
Both:
Both:
Heat Detectors:
Manual Pull Station:
DoorHoiders:
Sounding Devices: Visual Devices:
Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring :
Fire A]arm Systern Acceptable: NO, sn{oKE DETECTORS .{Rs REQLTTRED rNOCCUPANCY.
10' other corrections that are required by special occupancy or conditions.
Plans as submitted are acceptable: NO
f]ans checked by: CHRfS HUSKINSON Date: t0_5_03Please furnisii cornmen'rs back to the pian rev-iewer in the foliowing manner:Written Comments: X Newplans: X