HomeMy WebLinkAboutPLAN REVIEW LETTER - 04-00251 - Parkside Townhomes - ClubhouseI STATE OF IDAHO www.ci. rexburg.id.us P.O. Box 280 12 North Center Street Rexburg, ldaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg @ ci.rexburg.id.us Gu*f m**6**y I have deficiencies: 1. 10l16DAA3 John Dester Georgeto wn DeveloPment 2230 N. University PkwY Provo, VT 84604 Dear John" reviewed the drawings for the Parkside Clubhouse and have identified the following A new site plan was not provided with the drawing. Provide handicapped parking and identiffthe accessibfi route fromthe buiiding to the handicapped spaces and to the pedistrian walks. Id.entify dinrensions from the building to tlre other buildings and to the ProPerlY line. The plans must be stamped ty a Hcensed professional as per the 2000 International Building Code (IBC) Section 106.1. Provide structural calculations. submit manufaeturer's certificate of compliance for alt components as per IBC Section 16)13.5. Provide 1 1r. separation between the pool eqlripment loofir and the rest of the building. Identify the door to this room as a fire rated door' Identify exit signs. Please provide truss details before framing inspection' Energycalculations are required as per the 2000 International Energy Conservation Code. The energy code conopliance documents that,vou provided me for the Rexburg, Idaho parkside Clubhouse are for Spanish Fork Utah and were created using an outdated software. Please provide a new checklist using COM Check (available at energycodes.com). Be sure to pick the 2000 IECC and Rexburg, Idaho &om the drop down lists. 9. I have attached a copy ofthe Fire Department review to the back ofthis document. Please resolve any issues identified by tlen please provide me with 2 new copies of corrected plans. If you have any questions, please eive me a calT at 359-3020 ext. 324. Val Christensen Buildins Official 2. aJ. 4. 5. 6. 4t" 8. e;nv ,/ m,o6*ny STATE OF IDAHO P0. Box 280 1 2 North Center Street Rexburg, ldaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@srv.net REXB ITRG-MAD I S O]Y C O UI{TY EMERGEIVCY StrRWCES 26 NORTII CENTER STKEET REXBT]RG, IDAHO 83440 208-3s9-3010 208-3s9-3006 tAx 2000 International Fire Code Plan Review Building Nanee: GEORGETOWN Cr'T-IBHOUSE Buildins Address: IINKNOWN Plan Date: UNKNOWN Review Date: 10-5-03 Stories: ONE Type of Construction: V-B Occupanci; Classifi cation: A-3 Existing Floor A-rea: N1A l.{ew Consiruciion Floor Aiea: APPROXIMATELY 4,500 SQU'{RE FEnT I Required Fire Flow (Appendix B). 1750 GPII/TWO HOURS COMMENTS: FIRE FI-OW i\iAY BE REDUCED IF STRUCTURE HAS AN APPROVED AUTOMATIC FIRE SUPPRESSION SYSTEM INSTAILED' 2. Water Suppiy (Section 508, Appendix C) Required: YES fire Hydrant Location: TWO PROPOSED HYDRANTS fire Hydrant Flows: UNKNOWN Fire Flow Test Location: N/A Fire Flow Supplied By: N/A Other Approved Water Source: NONE Water Supply Acceptable: NO Fire Hydrant Location Acceptable: NO water Supply comments: uNr(NowN HTDRANT FLow, PLEASE pRowDE ENGINEERS CALCULATION FOR FLOWS. UNCLEAR OF'HTDRANT LOCATIONS, PLEASE PROyIDE IMPRO\rED SITE PLAN. 3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: yES Acceptable Width: NO Length: NO Sur ce: OK Complete Road Acceptable: NO comments: No srrE PLAN TNCLUDED wrrH BUTLDTNG pLANs. 4. Access Roads and Water Supply, including fire hydrants are required to be installed and made serviceable priorto and during time of construction (Section 501): comments: rF Nor TNSTALLED PRroR To CONSTRUCTTON AND MADE OPERATIONAI., A STOP WORK ORJER WILL BE ISSLIED. 5. Installation of portable fire extinguishers (Section 906) Required: yES Location shown: NOT SHOWN Type provided acceptable: NOT SHOWN COTNMENtS: NEED TO PROVIDE MINIMUM OF 2A1OBC EXTINGLqSHI,R nri KITCHT"N AREA, AT LEAST TWO OTHERS IN BUILDING WITHIN TRAVEL DISTANCES. 6. Automatic fire extinguishing systems (Section 903) Required: NO Type of system being instailed: NOT SHOWN Sprinkler system monitoring (Section 907) required: Comments: NONE 7. Standpipes (Section 905) required: NO Type required: Comments: 8. ventiiating hood and duct fire extinguisher system (section 609) required: No Type being provided: Automatic fuel shut-off required: Portable fue extinguisher shown: Comments: 9. Fire alarm systems (Section 907) required: yES Type of system required: Manuai: Automatic: X Type of system being provided: Manual: Automatic: Components of system shown: Smoke Detectors: Both: Both: Heat Detectors: Manual Pull Station: DoorHoiders: Sounding Devices: Visual Devices: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring : Fire A]arm Systern Acceptable: NO, sn{oKE DETECTORS .{Rs REQLTTRED rNOCCUPANCY. 10' other corrections that are required by special occupancy or conditions. Plans as submitted are acceptable: NO f]ans checked by: CHRfS HUSKINSON Date: t0_5_03Please furnisii cornmen'rs back to the pian rev-iewer in the foliowing manner:Written Comments: X Newplans: X