HomeMy WebLinkAboutNEWPORT FIRE PLAN REVIEW - 10-00054 - 370 W 7th S - South Gate Apts 12 Plex - Phase 126 NORTH CEIYTER STREET REXB(IRG, IDAHO 83440 REXBURG-MADIS0IVC0LINTY EMERGEIVCY SERVICES 208-359-3010 20s-359-3006 FAX 2000 International Fire Code Plan Review Building Name: NEWPORT CONDOMINIUMS Building Address: 300 BLOCK OF WEST 7rH SOUTH Stories: 3 Type of Construction: V-B Occupancy Classification' R-2 Existing Floor Area: N/A NewConstructionFloorfuea:APPROXIMATELY20,560SQUAREFEETEACH BUILDING 1. Required Fire Flow (Appendix B): 3'750 GPM/TIIREE IIOURS Comments:FIREFLowMAYBEREDUCEDIFEAC}IBUILDINGHASAFIRE SUPPNNSSION SYSTEM TIIROUGHOUT' 2. Water Supply (Section 508' Appendix C) Required' YES Fire HYdrant Location: OKAY Fire HYdrant Flows: UNKNOWN Fire Flow Test Location: N/A Fire Flow SuPPlied BY: N/A Other APProved Water Source: NONE Water Supply Acceptable: SEE COMMENTS Fire Hydrant Location Acceptable: YES Plan Date: 5-22'03 Review Date: 5'29'03 water Supply comments: PLEASE PRovrDE AN ENGTNEER'S ASSESSMENT OF WATER FLOWS PRIOR TO CONSTRUCTION. 3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: yES Acceptable Width: X Length: X Surface: X Complete Road Acceptable: YES Comments: NONE 4. Access Roads and Water Supply, including fire hydrants are required to be installed and made serviceable prior to and during time of construction (Section 501): comments: rF Nor TNSTALLED PRroR To CONSTRUCTTON AND MADE OPERATIONAL, A STOP WORI( ORDER WILL BE ISSUED. 5. Installation of portable fire extinguishers (Section 906) Required: yES Location shown: NOT SHOWN Type provided acceptable: NOT SHOWN comments. MTNTMUM srzE oF 2A10BC REQUTRED To BE MOUNTED rN EACII UNIT NEAR THE KITCHEN AREA. 6. Automatic fire extinguishing systems (Section 903) Required: YES Type of system being installed: NOT SHOWN Sprinkler system monitoring (Section 907) required: YES comments: PLANS REQUTRED To BE suBMrrrED To srATE pRroR To ISSUANCE OF A BUILDING PERMIT. 7. Standpipes (Section 905) required. NO Type required.Comments: 8. Ventilating hood and duct fire extinguisher system (Section 609) required: NO Type being provided: Automatic fuel shut-off required. Portable fire extinguisher shown: Comments: 9. Fire alarm systems (Section 907) required: YES Type of system required: Manual: Automatic: Type of system being provided: Manual:Automatic: Components of system shown: Smoke Detectors: X Manual Pull Station: Sounding Devices: Both: X Both: X Heat Detectors: Visual Devices: Door Holders:Duct Detectors:Flow Alarm: Sprinkler Valve Monitoring: REQUIRED Fire Alarm System Acceptable: NO, SEE COMMENTS BELOW i0. other corrections that arerequired by special occupancy or conditions: FIRE ALARM SYSTEM: PLEASE SUBMIT PLANS IN ADDITION TO THE FOLLOWING SUBMITTALS: ALARM CONTROL AND TOURBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER CONNECTION' BATTERY CALCULATIONS, CONDUCTOR TYPE AND SIZES' VOLTAGE DROP CALCULATIONSO MANUFACTURERS MODEL NUMBERS' AND LISTING INFORMATION FOR EQUIPMENT, EVICES AND MATERIALS AND INTERFACE CONNECTIONS. ADA UNITS SIIALL HAVE ALL IIORN/STROBE UNITS. PLANS MUST BE SUBMITTED PRIOR TO CONSTRUCTION OR A STOP WORI( ORDER WILL BE ISSUED' Plans as submitted are acceptable: NO Plans checked bY: CIIRIS HUSKINSON Date: 5-29-03 Please furnish comments back to the plan reviewer in the following manner: Written Comments: X New Plans: X t4t d",T;1[ r/"/, rt/rvEeD ;gz*q(S Ar Efts7 rry;rf LrlE ' S/ouu-P Bt Iu. ,-ADr l,rytfY SlVou $7or4a4- kre6 I AgarrT t Q klb{1Pof ':DPI I fp4u to€ Tcrt t'ptu b H r q'ftrs, l # of fleo<) ka7 @' 11eun ?tmer6ro6- /e &u/t D tNb9 ' Trtv r od Tr?t''t<tu o /l'tsLt DmePStoP5 ?Aou tqd '/" A,F hf'et l/rr"D $Qftfua- - & 5M V*rl flcre>ratd(/,r- 571t'<d' 'l i -) i ^ '. *t s-a'3 tV€,u)Vort Lond okn tn ru rfis .a r{.\ \.) I \s bn .x.s 7, 3, t/ t' 5. 6. 7,