I have reviewed the Main Street Station drawings that you have provided me and
have identified the following discrepancies:
1. A fence or a suitable buffer must be provided between parking areas and other
residential properties. Please provide fence or buffer at the East side ofthe
project alrng parking lot.
2. Turn the trash dumpsters so that our sirte loading trucks can access them
without having to back uP.
3. The Fire Department has marked fire lanes onto page S-2 ofthe drawings that
I will r€tum to you as your "approved set". I have attached a copy ofthe Fire
Department review to the back of this document. Please contact Chris
Huikinson at (208) 359-3010 in you have any questions concerning the Fire
Department review.
4. ThA gg7 Uniform Building Code (UBC) section 1103.1.9.3 requires all grade
level dwelling units to be Type "B" Dwelling Units. Please indicate this on
plans.
5. The entry balcony of the 3-bedroom "A" unit must be constructed as per the
1997 Uniform Building Code (UBC) section 1W6.3.2.3. This section requires
the walls around the entrance balcony and the ceiling to be one hour rated.
The code requires this when the occupancy ofthe exit is more than 10
persons. 3-bedroom units are frequently occupied by 6 persons.
6. Detail 6 on page 410 does not show fire separation in the crawl space. The
fle separation between the units must be maintained throughout. The pony
walls inthe crawl space and up to floor decking must be fire rocked.
7. Provide truss manufacturer specifications and detail sheets. I will need these
prior to framing inspection.
8. Please provide information identifying minimum foundation reinforcement as
per UBC section 1914.3.3.
Please provide me with two copies of any changes tlnt are made to the plans. Let
me know if I can be of any further assistance. If you have any questions, please give me
a call at 359-3020 ert. 324.
Sincerely, --
72
Val Christensen
Building Official
cc John Millar
Chris Huskinson
REXBI'RG MADISON COI'NTY FIRE DEPARTMENT
P.O. Box 280
25 North Center
Renburg, Idaho 83440
(208) 3s9-3010
L997 Unifo:rn Fire Code
PIan Review
Building Name: MAIN STREET STATION
Acceptable: width: YES
Turning Radius: YES
PLan Datez 4'L5'O2
RevLew Datez 4-30-02
Building Address: MAIN STREET BETWEEN 4* AND 5'* WEST
Stories: 2 Type of Construction: V-N
Occupancy Classification: R-1, B Existing Floor Area: N/A
New Construct.ion Floor Area: APPROXIMATELY 5,800 SQUARE
FEET/BUII.DING
1-).Required Fire FIow (Appendix rrr-A): 2,OOO GPM/Two HOURS
Comments: FIRE FLOW MAy BE REDUCED Bl 75% IF BUIIJDING IS EQUIPPED
WITH AII APPROVED AUTOMATIC SPRINKLER SYSTEI TO NO IJESS TEA]I 1' 500
GPM.
2) .Water Supply (Article 9, Section 903) Required: YES
Fire HydranL l-,ocation: A-5, A-5, A-11
Fire Hydrant, Flows: OK
Fire Flow Test l-,ocation: A-5, A'5' A-11
Fire Flow Supplied By: FD :
Other Approved Water Source: NONE
water Supp1y Acceptable: NO, SEE CO!{MENTS
Fire Hydrant Location Acceptable: NONE SHO!{N ON PLA}IS
Water Supply Comments: EXISTING HIDRAIITS ARE TOO FAR AWAY TO BE
UTILIZED. PROPOSED SITE PLAII SHOWS NO NEW HY-DRAIITS. DEVEIJOPIIENT
SILALL HAVE TWO EYRDAIITS WITHIN 450 FEET OF EACH BUILDING.
3. ) Fire Apparat,us Access Roads (Article 9 Section 9O2)
Required: YES
I-,ength: YES Surf ace : YES
Grade: OK Vehicle Vertical-: YES
Clearance: OK Turn Arounds: N/A
Complete Road Acceptable: YES
CorrrneNLS: NORTII SIDE OF PROPERTY SHOIIS A 2O.FOOT WTDE ROAD EXITING
THE PROPERTY. TIIIS ROAD TO BE SIGNED AI{D CT'RBS PAIIITED RED FOR FIRE
APPARATUS ACCESS. AREAS MARKED IN RED ON SITE PLA}T S-2 TIIDICATE
FIRE I.A}IE TO BE STGNED AIID WITH THE CURBS PAINTED RED.
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceabl-e Prior To And During
Time Of Construction (Art.icle 9 Section 901.3) : YES
Cornrnents: IF NOT INSTALLED PRfOR TO CONSTRUCTION A STOP WORK ORDER
WII,'IJ BE ISSUED.
5).Installation Of Portable Fire Extinguisher (Article 10 Sectj-on
1-002) Required: YES l-,ocation Acceptable: NOT SHOWN
Type Provided Acceptable: NOT SHOWN
Conrnent,s: PROVIDE AT LEAST ONE EXTINGUISHER PER IINIT, UINIMITM SIZE
OF 2AlOBC. CI.UBHOUSE AI,SO NEEDS TO BE PROVIDED WITII ONE FIRE
EXTINGUISHER PER AREA.
6).Automatic Fire Extinguishing Syst,ems: (Article 10 Section 1003
Required: NO Type Of System Being fnstalled:
Sprinkler System Monitoring Required (Article 1-0 Section 1003.3)
Required:Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required:Comments:
8).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 1,006.2) Required: IINKNOWN Type Being Provided:
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4):
Portable Fire Extinguisher Shown (Article 10 section 1006 .2.2) ,
CoTmnenLs: IN COMMT'NIIY BUTTDING PIJA}IS IIIDICATE A KITCHBI, ![EED MORE
INFORMATIOII OF COOKING FACILITIES TO BE PROVIDED.
9) .Fire Alarm Systems (Article 10 Sect,j-on 1007)Required: YES
Type Of System Required: Manual: Automatic: YES Both:
Type Of System Being Provided: Manual: Automatic: YES Both:
Components Shown: Smoke Det.ectors: YES Heat Detectors: NO
Duct Detectors:Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Cormnents: SMOKE AIID HEAT DETECTORS REQUIRED III COMMON AREAS SUCH AS
IJAI'IIDRIES, RECREATION ROOMS' I{ECIIA}IICAI, ROOMS'
10).Other Corrections That Are Required By Special Occupancy Or
condiLions: IIAIIDICAPPED ItNITg IIIDICATED, IF TYPE ft A# MUST BE
pRovrDED wrrH HoRN,/STROBE I'NTTS THROUGHOUT rN ADDTTTON TO SMOKE
DETECTORS.
Manual Pul-1 SLation:
Door Holders:
P1ans As Submitted Are Acceptable: NO
Plans Checked By: CIIRIS EUSKINSON
Please furnish cornntents back Lo the plan
manner: Written Comments: YES
Sounding Devices: Visual Devices:
Date: 4-3O'02
reviewer in the following
New Plans: YES