HomeMy WebLinkAboutFIRE PLAN - 01-00049 - Dr Brad Egbert Office - New CommercialREXBI'RG MADTSON COT'NTY FIRE DEPARTMENT
P.O. Box 280
25 North Cenler
Re:<burg, Idaho 83440
(208) 359-3010
I
Building Name: Dr. Brad Egbert Medical Office
Building Address: Bond Street
Stories: one Type of Construction: V-l[
Occupancy Classification: B Existing Floor Area: Nr/e
New Construction Floor Area: Approximately 24OO sq. feet
1).Required Fire Flow (Append.ix III-A): 1'500 GPM for thro hours
Comments: Iilater suppJ-y may be reduced by 50% if 'rr approved
automatic sprinkler syste'n is instalLed.
2).Water Supply (Art,icle g, Sect,ion 903) Reguired: YES
Fire Hydrant, Location: Bond Street: B-54, 8-56, B-58
Fire Hydrant Flows: OK
Fire Flow Test l-.,ocaEion: Sa'ne
Fire Fl-ow Supplied By: FD
Other Approved Wat.er Source: None
Wat.er Supply Acceptable: YES
Fire llydrant lrocation Acceptable: YES'
Wat,er Supply Cofiments: NONE
3. ) Fire Apparatus Access Roads (Artiele 9 Section 902)
1997 Uniforrr Fire Code
Plaa Review
Required: YIES
Accept,able: width: YIES
Turning Radius: N/A
Clearance: OK
Complet.e Road AccepLable:
Length: tlES Surface: Paved
Plau DaLe: 9/25lAL
Review Date: LL/5/OL
Vehicle Vertical: OKGrade: OK
Turn Arounds: OK
YES
4) .Access Roads and water supply, Includ,ing Fire Hydrants Are
Reguired To
'ee
inst.aLled And Made Serviceable Prior To And' During
Time Of Constrrrct,ion (Article 9 Sect'ion 901'3) : YES
Comments:
5).InstaLlation Of portable Fire Extinguisher (Article 10 Section
1OO2) Required.: YEs Location AcCeptable: Not shovrrr
Type Provided Acceptable: Not Sbowa
Corments: Need, to provid.e at least two fire extingrishers, ninimrm
size of 2A-108C
6).Automatic Fire Extinguishing Systems: (Article L0 Section 1003
Required: NO Type Of System Being Installed:
sprinkler system Monitoring Required (Article 10 Section 1003-3)
Reqr:ired:Comment,s:
8).Fire Alarm Systems (Article 10 Section 1007)Reqqired: NO
Type Of System Required: Manual: Automat'ic:Both:
Tlpe Of, System Being Provided.: Manual: AuLomatic: Both:
Components Of System Shown: Smoke DeLectors:Heat Detectors:
Manual Pu1l St.ation:
Door Holders:
Sounding Dewices: Visual Devices:
Duct DeLectors:Flow Alarm:
Sprinkler Valve Monitoring: Fire A1arm SysLem Accept'able:
10).Other Corrections That, Are Requined By Special Occupancy Or
Conditions: None
Plans As Submit,ted Are Accepuable: IIES
Plans Checked By: Chris Euskinson
Please furnish comrnent.s back to the plan
nanner: Written Cornments: New
DaLe:11-5-01
reviewer in the following
Plans: