HomeMy WebLinkAbout1999 FIRE PLAN REVIEW - 00-00032 - Madison High School - New Athletic BuildingRE:(BI'RG I{ADISON COTNflTY FIRE DEPARTI4ENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
Building Name: Madison High School Athl-etic Buildinq
Buildinq Address: ? East 2"d North
Stories: Two Type of Construction: V-N
Occupancy Classification: E-l- Exi-sting Floor Area: N/A
New Construction Floor Area: 15r000
1994 Uniforlm Fire Code
P1an Review
1).Required Fire Flow (Appendix III-A) :
2).Water Supply (Article 9, Section 903)
Fire Hydrant Location: 45! East 2"" North
PJ-an Date: 09-02-99
Review Date: 10-12-99
3,000 qpm
Required: Yes
134 Madison Ave 400 East
2"d North
Flre Hydrant Flows: 3,000 G 20 psi
Fire Flow Test Location: 460 East 2"d North
Fire Flow Supplied By: Fire Department
Water Supply Acceptable: Yes
Fire Hydrant Locatj-on Acceptable: Yes
Water Supply Comments: North well- was not on for the test
3. ) Fire Apparatus Access Roads (Article 9 Section 9O2)
Required: Yes Complete Road Acceptable: $o
Comments: Provide new site plan showing access to buildins
4).Access Roads and Water Supply, lncluding Fj-re Hydrants Are
Required To Be Tnstal-l-ed And Made Serviceable Prior To And Durinq
Time Of Construction (Article 9 Section 901-.3): N/A
-
Plan Revi-ew
Page 2
5) .Installation Of Portable Fire Bxtj-nguisher (Article 10 Section
Not shownL002) Required: Yee Location Acceptable:
Type Provided Acceptable: Not Shown
Comments: Minimqm 2-A L0-BC within 75 feet travel distance
6).Automatic Fire Extinguishing Systems: (Articl-e 10 Section 1003
Required: No Comments : Sec. 1-003 .2.4 . f e""gp!.gtt_!
7).Standpipes (Article 10 Section 1004) Required: No
B).Ventilating Hood And Duct Fire Extinguishing System (Articl-e 10
Section L006.2) Required: No
Comments: No cooking producinq grease l-aden vapors
9) .Fire Alarm Systems (Articl-e 10 Section l-007)Required: Yes
Type Of System Required: Manual
Type Of System Being Provided: Not shown
Fire Alarm System Acceptable: Nq, provide fire alarm svstem plan
Plans As Submitted Are Acceptable: No
Pl-ans Checked Bv: Dee Owens Date:10-12-99
Please furnish comments back to the plan reviewer in the followinq
Manner: I will need a site plan showinq access and fire alarm
svstem plan