HomeMy WebLinkAboutFIRE PLAN REVIEW - 97-00036 - Papa Kelsey's - RemodelREXBURG IIADISON COI'NTY FIRE DEPARIME}ilT
P.O. Box 280
26 North Center
Rorburg, Idaho 83440
(208) 3s9-3010
Storles: 1 Tvpe of Construction:
Occupancy Classiflcation: A-3 Existinq Floor Area: 3360
1).Required Fire Flow (Appendix III-A) : 1500 q.p.m.
2).Water Supply (Article 9, Section 903) Required: yes
Fire Hydrant Location: Center I 1st South. 50 South Center, 1st
West & 1st South
InTa.|_ ar Qrrnnl rz Annonf rh I a. VCS
Fire Hydrant Locatj-on Acceptable: Yes
3.)Fire Apparatus Access Roads (Article 9 Section 902)
L994 Uniform Fire Code
PIan Review
Buildinq Name: Papa Kelsev's
Building Address: 40 West 1st South
Required: Yes
Acceptable: Width: Yes Length: Yes
Turni-ng Radlus: Yes Grade: Yes
Clearance: Yes Turn Around: NA
P].an Date: 09-09-9?
Review Date z O9-L6-97
(rr rf .ar-o. Yaq
Vehicle Vertical
Complete Road Acceptable: Yes Comments: Existino narkino lot
4 ) .Access Roads and Water Supply, fncluding Fire Hydrants Are
Requlred To Be fnstalled And Made Serviceabl-e Prior To And Durinq
Time Of Construction (Article 9 Section 901.3) Yes
5).fnstallation Of Portable Fire Extinguisher (Article 10 Section
Plan Review
P:no ?
L002) Required: Yes Location Acceptable: Not Shown
Type Provided Acceptable: Not shown Comments: Size and
glacement must be approved before openina
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: No
7).Standpipes (Article 10 Section 1004) Required: No
B).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 7006.2) Required: No grease laden vapors
9).Fire Alarm Systems (Article 10 Section 7001)
Required: No
10).other corrections That Are Required By special occupancy or
conditions: chain co2 tanks to wal-l-, panic hardware required on
both rear exit doors
Plans As Submitted Are Acceptable: Yes
Plans Checked By: Dee Owens Date: 09-L6-97