1994 Uniform Fire Code
Plan Review
Building Name: Hollvwood Video
Building Address: 160 West Main
Qfnri aq. OnoJUV! -
Type of Construction: V-N
OccupancY Classification: M Existing Floor Area: N/A
New Construction Floor Area: 7'200 square feet
1).Required Fire Flow (Appendix III-A) : 3'000 q'p'm'
2).Water Supply (Article 9, Section 903) Required: Yes
Fire HYdrant Location:
Fire HYdrant Flows:
Fire Flow Test Location:
Fire Flow SuPPlied BY: Fire DePt '
Other APProved Water Source: N/A
Water SuPPIY AccePtable: Yes
Fire Hydrant Location Acceptable: Yes
3. ) Fire Apparatus Access Roads (Article 9 Section 9A2)
Required: Yes Complete Road AccePtabie: Yes
,1).Access Roads and water Supply, Including Fire Hydrants Are
Required To Be Instalted And Made serviceable Prior To And During
Tine Cf Construction (Article 9 Section 901'3) Yes
5).insrailatj-on of Portable Fire Extinguisher (ArticIe 10 Section
Plan Date: 03-06-98
Review Date: 03-17-98
Plan Review
Page 2
L002) Required: Yes Location AccePtable: Not shown
Type provided Acceptable: Not Shown Conalents: Minimum 2-A 10-BC
I nnrf od .aq nor TII-C Sf anclard 10-1r{rr..rr \.\/ rr!, uu! vtv veqtrss!\
6).Automatic Fire Extinguishing systems: (Article 10 section 1003
Required: No Type Of System Being Installed: None
Comments: M occupancy under 12,00 sq' Ft'
7).Standpipes (Article 10 section 1004) Required: No
8).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section L006.2) Requlred: No
Comments: No cooklnq iacilitv shown
9).Fire Alarm Systems (Article 10 Section 1007) Required: No
Plans As Submitted Are Acceptable: Yes
Ptans Checked By: Dee Owens Date: 03-17-98