19911 Unifor:n Fire Code
Plan Review
PIan Date: Ju1y 97
Review Date: 9-8-97
Rrri 'l rli nrl ]rT-amo. ,TRhI I-Ioal f h rnrl Inlol frra Rrli I di nnuu!lvrltv t\qltlE sfrv yrvr!u!9 uuIaulllv
Buildlng Address: 333 Walker Drive
Stories: one Tvpe of Constructlon: V-N
Occupancy Classification: B Existing Floor Area: New construction
New Construction Floor Area: 8,640 square feet
1) .Required Fire Flow (Appendix III-A) : 2,500 q.p.m.
, \ TrTr1_ ar Qrrnnly (Article 9 , Section 903 ) Required: Yesa/.rrquu! vu-y-y-
Fire Hydrant Location: B-47 300 Walker Drive, B-37 400 N. 3rd E.
Fire Hydrant Flows: 4,045 G 20 psi
Flre Flow Test Location: B-47, B-37
F-i ra F-l nr"r (rrnnl i orl Rrr. E-i ra Tlan-: r1- manJ-vuvv Dy . L !!v uvvq! urLLUllL
Water Supply Acceptable: Yes
Fire Hydrant Location Acceptable: Yes
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: Yes
4 ) .Access Roads and lt{ater Supply, Including Fire Hydrants Are
Required To Be fnstalled And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3) Yes
Comments: Hvdrants are in service now and Walker Drive is oravel
5).fnstallation Of Portable Fire Extinauisher (Article 10 Section
Plan Review
Page 2
L002) Required: Yes Location Acceptable: Not shown
Comments: Need size andTvpe Provided Acceptable: Not shown
location
6\ Arrl-nmefir- Firo Ewf inorrishino Srrqfoms. (Arf ir-lo 10 SeCtiOn 1003' \zf!
Required: No
7\ Qj_.anrlninaq /ArJ_ inla 1n Qnnrinn 1nn/\ Qarrrrirod . \Tn/ / . JLolruyr}/sJ vuL-Lr\Jri r\JV1l ngLlurrg\.r. ry.
B).Fire Alarm Systems (Article 10 Section 1007) Required: No
'l'\7nA t )?- \lZeiam Har nfr vTA\71alad. Hn r nr vvv uvuuv!!l UgrtIV L!VVIUSU. UVLII
Components Of System Shown: Smoke Detectors:l9 Manual Pull
Devices: 9Station:4 QnrinrJ'innr f)arzinoq. 0 Vi sual
Fire Alarm System Acceptable: No
Plans As Submitted Are Acceptable: No
Plans Checked By: Dee Owens Date: 9-8 97
Please furnish comments back to the plan reviewer in the following
manner: I need the detailed plans of the fire alarm system