HomeMy WebLinkAboutPLAN REVIEW - 96-00029 - Dr Robert Walker Dental Office - New Buildinga REXBURG I.IADISON COUNTY FIRE DEPARTI'iENT P.O. Box 280 26 North Center Rerburg, Idaho 834{0 (208) 3s9-30r'o 1994 Uniform Fire Code Plan Review Plan Date: 01-15-96 Review Date: 10-02-95 Building Name: Dr. Robert L. WaIker Profession-al- Bglf-ding Ash Street and lst--€-qu!hBuilding Address: Stories: 2 Type of Construetion: !r--N Existing FLoor Area: N/A Oceupancy Classifieation: B New Construetion Floor Area: ?'026 sq' Ft' L).Required Fire Flow (Appendix III-A): ?'-Ls*-o--gpu Comments: Requires two fire hvdrants 2).Water Supply (Rrtiele g ' Section 903) Required: Y-e-g- Fire Hydrant Location: D-12 lst South and Ash Fire Hydrant Flows: 2,125 at 20Psi Fire Flow Test Location: D-I2 Fire Flow Supplied By: Fire Department Other APProved Water Souree: NIA tlater SuPPIY AccePtable: No Fire Hydrant toeation Acceptable: NQ water supply Comments: A tlre hvdrant yill neesl-te-b-e^-added' in lhe f rqrn -ats-gYe- 3.)fire Apparatus Aeeess Roads (nrticle 9 Seetion 902) Required: Yes Aeceptabl e:Width: 30 ft. Length: Okav Surfaee: QEaY PIan Review Page 2 Turning Radius: okaY Grade: OL-all Vehiele Vertieal Clearanee: Okav Turn Around: SkgY Complete Road AccePtable: I-ee Comment s : 4).Aecess Roads and water supply, Ineluding Fire Hydrants Are Required To Be Installed And l.tade servieeable Prior To And During Time of construction (Artiele 9 section 9c1.3) Yes Comments: As close as Possible 5).InstaIIation Of Portable Fire Extinguisher (Rrticle 10 Section 1002) Required: Yes Location AceePtable: Not shown Type Provided Acceptable: Not shown Connents: t'{inirnrm 2-A IO-BC 6).Automatic Fire Extinguishing Systems: (Rrtiele 10 Section 1003 Required: No ?).standpipes (ArtieIe 10 seetion 1004) Reguired: N--o- 8).VentiIating Hood And Dret Fire Extinguishing system (ArtieIe lC Section 1005. 2 ) Required: N-o 9).fireAlarmsystems(ArtieleICSeetionLC0?) Required: No L0).other correetions That Are Required By speeial oceupaney or conditions: see attached section for medieal qases. PIans As Submitted Are Acceptable: Yes Plans Checked BY: Dee Owens Please furnish corments back Date: L0-02-96 to the plan reviewer in the following manner: FROM : Seetion 7404 Article 14 Section 7 4A4 - MEDICAT GAS SYSTEMS 7404.L Genera1. Compressed gases at hospitals and similar facilities intended for inhatation or sedation including, but not limited to, analgesia systems for dentistry, podiatry, veterinary and similar uses shall be in aeeordance with seetion 7404 in addition to other reguirements of Artiele 74' 7 404.2 SupplY tocation. 7404,2.L Interior supply loeation. 74A4,2,L.1 General . Medieal gases shalI be stored in areas dedieated to the storage of sueh gases without other storage or uses. When eontainers of medieal gases in quantitres greater than the permit amount are troeated inside buildrngs, they shall be in a onl-hour exterior room. a one-hour interior room or a- gas eabinet in aeeordanee with seetions 7 404.2.L.2 , 7 4A4.2 .L ' 3 0r 7 404,2 .L.4. 7404.2.L,2 One-hour exterior rooms. A one-hour exterior room shall be a room or enelosure separated from the rest of the i;iiding by not less than one-hour-rated fire-resistive eonstruction. Openings between the room or enelosure and interior "p".." shall be selflclosing smoke- and_draft-control assemblies triving a fire-proteetion rating of not less than one hour' Rooms shall have at least one exterior wall which is provided with at least two vents. Each vent shall not be less than 36 square in"tt.t (0.023 m2) in area. One vent shall be within 6 inches aiat.+ titt"l of the floor and one shall be within 6 inehes (L52.4 mm) of the eeiling. Contaitt.tt of medical gases shall be provided with at least one fire sprinkler to provide container eooling in case of fire. 7 4A4.2,L.3 One-hour be provided for the within the room. The the exterior. MakeuP exterior. Both separate air streams shall be enelosed in a one-hour-rated shaft enelosure from the room to the exterior. Approved mechanieal ventilation shall be in aeeordance with the Meehanical code and provided at a minimum rate of I eubie foot per minute per square foot (5.1 L/s per m2) of the area of the room. 74A4.2.L,4 Gas eabinets. Gas eabinets shall be in aeeordanee wrth the following: L. Operated at a negative pressure in relat'ion to surrounding area, interior room. t{hen an exterior wal l cannot ioo*, automatic sprinklers shall be installed room shal I be exhausted through a duct to air to the room shal I be taken from the 2. Provided with self-elosing Iimited-aeeess ports or noneombustible windows to give aeeess to equipment eontrols. The average veloeity of ventilation at the faee of aeeess ports or windows shall not be less than 200 feet per minute (51 m/min.) with a minimum of I50 feet per minute (45.7 mlmin.) at any point of the aceess port or window, 3. Connected to an exhaust system, 4, Provided with a self-elosing door, 5. construeted of not less than 0.097-ineh (2.45 mm) (tz qage) steel, and 5. Internally sprinklered. 74O4,2.2 Exterior supply loeations. Oxidizer medical gas systems Iocated on the exterior of a building with quantities greater than the permit amount shall be located in accordanee with Section 8004. 7404.2.3 Medical gas systems. ltedieal gas systems ineluding, but not limited to, distribution piping, supply manifolds, connections, pressure regulators, and relief devices and valves, shall be in aeeordance with u.F.c. standard 74-2 and the general provisions of Article 74. - f REXBURG I.{ADISON COUNTY FIRE DEPARTMENT P.O' Box 280 26 North Center Rexburg, Idaho 83440 (208) 3s9-3010 L994 Uniform Fire Code Plan Review Building Name: Building Address: Ash Street and lst South Stories:2 Occupancy classification: B New Construction FIoor Areaz 7 'O26.9-q' Ft' 1).Reeuired Fire FIow (Appendix rrI-A): ?---?5-0--qPB c ommen t s : Bgg-lr.LL gs. l,:rp*ti:-e =bvd_r ea!-s- 2).Water Supply (Rrtiele g, Seetion 9C3) Required: Yes Fire Hydrant tocation: D:L?- lst_SgutL--an*{ Sg-b Fire Hydrant Flows: 2,126 at 2CPsi Fire Flow Test tocation: D-12 Fire EIow Supplied By: Fire Department Other APProved l{ater Source: N/A Water SuPPIY AccePtable: No Fire Hydrant Location Acceptable: No Water SrrPPlY Comments : Type of Construction: V-N Existing Floor Area: N/A PIan Date: 0L-15-96 Review Date: 10-02-96 from above. 3.)Fire Apparatus Aeeess Roads {Rrtrele 9 Seetion 902) Required: Yes Aeeeptabl e: Width: 39 :[t .Length: -OkaY- Surfaee: 9kaJ Plan Review Page 2 Turning Radius: Okav Grade: Okay Vehicle Vertical Clearanee: Okav Turn Around: Okay Complete Road Aceeptable: yes Comments: 4).Aecess Roads and gfater supply, Ineluding Fire Hydrants Are Required To Be Installed And Made Servieeable Prior To And Durinq Time Of Construetion (Artiele 9 Seetion 90I.3) yes Comments: As close as possi-b_le 5).Installation of Portable Fire Extinguisher (ArtieIe lC Seetion 1002) Required: Yes Loeation Aceeptable: Not shown Type Provided Acceptable: Not shown with maximum travel distanee of 75 feet. Corurents: Minimum 2-A IC-BC 6).Automatic Fire Extinguishing Systems: (erticle 10 Section I003 Required: No ?).Standpipes (ertiele 10 Seetion 1004) Reguired: No 8).Ventilating Hood And Drct F'ire Extinguishing System (RrtieIe I0 Seetion 1005.2) Reguired: No 9).Fire Alarm Systems (Artiele l-C Seetion 1002) Required: No 10),other correetions That Are Required By special oeeupaney oy Conditions: See attaehed seetion for medieal qases. PIans As Submitted Are Aeeeptable: Y.e_S Plans Checked By: Dee Owens Date: 10-C2-96 P1ease furnish comnents back to the plan reviewer in the following manner: FROM : Section 74A4 Artiele 7 4 Section 7 444 - MEDICAL cAS SYSTEMS 7404.L GeneraI. Compressed gases at hospitals and sirnilar facilities intended for inhalation or sedation ineluding, but not Iimited to, analgesia systems for dentistry, podiatry, veterinary and similar uses shall be in aeeordanee with Seetion 7404 in addition to other requirements of Artiele 74, 7404,2 Supply Location. 7404.2.L Interior supply location. 74O4.2.L.1 General , Medical gases shall be stored in areas dedicated to the storage of sueh gases without other storage or uses. 9fhen containers of medical gases in quantities greater than the permit amount are loeated inside buildings, they shall be in a one-hour exterior room, a one-hour interior room or a gas cabinet in aeeordance with Seetions 7 4A4.2.L.2 , 7 4C4. 2. L.3 or 7 404.2.L.4. 1444.2.1.2 One-hour exterior rooms. A one-hour exterior room shall be a room or enelosure separated from the rest of the building by not less than one-hour-rated fire-res:.stive construction. Openings between the room or enelosure and interior spaees shall be self-closinq smoke- and draft-eontrol assemblies having a fire-proteetion rating of not less than one hour. Rooms shall have at least one exterior wal1 which is provid.ed '*ith at least two vents. Eaeh vent shall not be less than 35 sguare inehes (0.023 m2) in area. One vent. shall be within 6 inehes (152.4 mm) of the floor and one shall be within 6 inehes (152.4 mm) of the eeiling. Containers of medieal gases shall be provided with at least one fire sprinkler to provide container eooling in case of fire. 7404,2.L.3 One-hour interior room. When an exterior waI1 cannot be provided for the room, automatie sprinklers shall be installed within the room. The room shall be exhausted through a duct to the exterior. Makeup air to the room shall be taken from the exterior. Both separate air streams shall be enclosed in a one-hour-rated shaft enclosure from the room to the exterior. Approved mechanical ventilation shall be in accordance with the Uechanieal Code and provided at a minimum rate of I eubie foot per minute per square foot (5.1 L/s per m2) of the area of the room. 7 404.2,L,4 Gas eabinef s with the following: Gas eabinets shal I be in aeeordanee 1. Operated at a negative pressure in relation to surrounding area, 2, Provided with self-elosing lirnited-aceess ports or noneombustible windows to give aeeess to equipment controls. The average veloeity of ventilation at the face of aeeess ports or windows shall not be less than 200 feet per minute (6I m/min.) with a minimum of 150 feet per minute (45.? m/min.) at any point of the aecess port or windovr, 3. Connected to an exhaust system, 4, Provided with a self-cIosinE door, 5. Construeted of not Iess than 0.09?-ineh {2,45 nrm) (L2 gage) steel, and 5. Internally sprinklered. 74A4,2.2 Exterior supply loeations. Oxidizer medieal gas systems Ioeated on the exterior of a buildinq with guanlities greater than the permit amount sha1l be loeated in aeeordanee w:-th Section 8004, 74A4.2.3 Medieal gas systems. Medieal gas systems including, but not limited to, distribution piping, supply manifolds, eonnections, pressure regulators, and relief devices and valves, shall be in aceordanee with U.F.C. Standard 74'2 and the general provisions of Artiele 74,