HomeMy WebLinkAboutDOCS - 02-00054 - Verizon Wireless Cellular - GeneratorMEMO:
TO:
FROM:
DATE:
RE:
Chris Huskinson
Fire Inspector
TO WHOM IT MAY CONCERN
CHRIS HUSKINSON, FIRE INSPECTOR
August 6, 2002
VERIZON WIRELESS GENERATOR ROOM
TO WHOM IT MAY CONCERN:
Upon review of the drawings submitted the following items need to be addressed:
1. NONE
If there are any questions please feel free to contact me.
4/29/2003
Richard Smith
Dick Smith Farms, INC.
637 Millhollow RD.
Rexburg, ID 83440
Dear Richard,
Val Christensen
Building Official
c.c. John Millar
Chris Huskinson
STATE OF IDAHO
www.ci.rexburg.id.us
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359 -3020
Fax (208) 359 -3022
e -mail rexburg @ci.rexburg.id.us
I have reviewed the drawings for and have only one concern.
The site plan shows an inadequate 5' setback on the back and side of the property to the
utility shed. At this time it will not be a problem as we will consider this lot as part of the
larger overall parcel. However, it will be necessary in the future to include the proper
setbacks required for side and back yard setbacks if this lot is ever adjacent to another
developed lot.
If you have any questions, please give me a call at 359 -3020 ext. 324.
July 31, 2002
Val Christianson
City of Rexburg
12 North Center
PO Box 280
Rexburg, ID 83440
Re: Request for Building Permit for addition of generator equipment to
existing Verizon Wireless cellular communications site — REXBURG
Dear Val Christianson:
!f
MERICOM'
C 0 R P O R A T 1 O N
Verizon Wireless respectfully seeks approval of a building permit for purposes of adding
a generator for back -up power at an existing cellular communications site. The project is
located in the NW 1 /4 of section 33, T. 6 N., R. 40 E., on a parcel owned by Dick Smith
Farms Inc.
Attached please find two sets of 11 x 17 drawings of the proposed project, signed and
wet - stamped for your review. Also attached is a check in the amount of $181.25 for the
permit fee, based on construction costs of $10,000. The contractor that will complete
the work will answer any specific questions required to obtain the permit.
If you should need any further information to complete the submittal or should you have
any questions at all, please feel free to contact me at (916) 920 -7900 or at the
Sacramento address listed below.
Thank you very much for your assistance.
Kind Regards,
Alycia Moulton
Representative for Verizon Wireless
Enclosures
4700 Northgate Boulevard - Suite 160, Sacramento, CA 95834
Phone: (916) 920 -7900 Fax: (916) 920 -2343
GENERAL NOTES
ADA COMPLIANCE: PCS FACILITY IS NOT STAFFED
AND NOT NORMALLY OCCUPIED.
LEGAL DESCRIPTION
SITE PARCEL NO:
SITE NAME: ID6 REXBURG
LEGAL DESCRIPTION:
NW 1/4 OF SEC. 33, T6N, R40E, B.M., MADISON
COUNTY, IDAHO
PROJECT SUMMARY
INSTALLATION OF VERIZON DIESEL GENERATOR
EQUIPMENT IN EXISTING SITE
PROJECT INFORMATION
SITE ADDRESS:
1/3 MILE NORTH FROM THE INTERSECTION
OF 2000 SOUTH AND MILL HALLOW
ROAD, WEST SIDE OF ROAD.
ZONING CLASSIFICATION: N/A
AREA OF CONSTRUCTION (SQ FT): 45 SO. FT.
OCCUPANCY CLASSIFICATION: U (UNMANNED
TELECOMMUNICATIONS FACILITY)
PROJECT DIRECTORY
OWNER: DICK SMITH FARMS, INO. & AMERICAN TOWER CORP.
637 MILL HOLLOW RD
REXBURG, IDAHO 83440
APPLICANT: VERIZON WIRELESS
5295 S. 300 W. SUITE 175
MURRAY, UT. 84107
AGENT: MERICOM CORPORATION
429 LAWNDALE DR.
SALT LAKE CITY, UT. 84115
(801) 486 -0858 FAX
CONTACT: JIM ANDERSON (801) 486 -3171
ENGINEER: MERICOM CORPORATION
4700 NORTHGATE BLVD. SUITE 160
SACRAMENTO, CA 95834
CONTACT: MARK NANNEY
(916) 679 -0343
DRAWINGS
T -1 TITLE SHEET
E -1 ENLARGED SITE PLAN
E -2 ONE —LINE DIAGRAM
E -3 DETAILS
APPROVE>s. ' A 't52-2._.-
BUI LD!NG'NSPEO TOR
SYMBOLS
EXISTING CONSTRUCTION TO REMAIN
CONCRETE
GYPSUM BOARD
;.c PLYWOOD
2Z FINISH WOOD
® WOOD FRAMING
VI
EssEE GLASS
START POINT FOR CONSTRUCTION
OR P.O.C.
NEW DENOTES CONTRACTOR PROVIDED
AND INSTALLED UNLESS
NOTED OTHERWISE
STONE WALL
WOOD BLOCKING
ALIGN
BME TAPERED INSULATION
EXISTING CONSTRUCTION TO BE REMOVED RIGID INSULATION
NEW PARTITION (SEE PLAN) INSULATION
CONCRETE BLOCK
GRAVEL BASE
— GAUGE METAL
STEEL
IME ACOUSTIC CEIUNG PANEL
1 - 1FLUORESCENT LIGHTING
1111 1111 FIXTURE
• SUPPLY AIR DIFFUSER
• RETURN AIR REGISTER
(33 ROOM NUMBER
t 1) DOOR NUMBER
O KEY NOTE
NEW DOOR
E ) EXISTING DOOR
DETAIL /SECTION NUMBER
SHEET NUMBER
EARTH
DETAIL /SECTION NUMBER
SHEET NUMBER
ABBREVIATIONS
AB ANCHOR BOLT GA GAUGE R RISER
AC ASPHALTIC CONCRETE GALV GALVANIZED REQD REQUIRED
A/C AIR CONDITIONING GL GLASS RD ROOF DRAIN
ACOUS. ACOUSTIC(AL) GR GRADE RM ROOM
ADJ ADJUSTABLE GYP GYPSUM RO ROUGH OPENING
A.F.F. ABOVE FINISH FLOOR RWD REDWOOD
HC HOLLOW CORE
HM HOLLOW METAL
HORIZ HORIZONTAL S SINK
HR HOUR SC SOLID CORE
HT HEIGHT SCHED SCHEDULE
SECT SECTION
ID INSIDE DIMENSION SHLVS SHELVES
C COURSES INS INSULATION
CAB(S) CABINET(S) TNT NTERIOR SHT SHEET
CEM CEMENT SIM SIMILAR
CL CHAIN LINK JT JOINT SPECS SPECIFICATIONS
CLOS CLOSET SS STAINLESS STEEL
CLG CEILING LAM LAMINATED STL STEEL
E LAV LAVATORY STOR STORAGE
CLG CLEAR
COL COLUMN
LBS POUNDS STRUCT STRUCTURAL
CONC CONCRETE LT UGHT SUSP SUSPENDED
CONST CONSTRUCTION MANUF MANUFACTURER
CONT CONTINUOUS MAX MAXIMUM TD TISSUE
CORR CORRIDOR MECH MECHANICAL DISPENSER
MIN MINIMUM THK THICK
MISC MISCELLANEOUS TS TUBE STEEL
ML METAL LATH PM TYPICAL
MO MASONRY OPENING
MS MACHINE SCREW UNO UNLESS NOTED
MTD MOUNTED OTHERWISE
MTL METAL
ARCH ARCHITECTURAL
BL BUILDING
BLKG BLOCKING
BOT BOTTOM
BSMT BASEMENT
DBL DOUBLE
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIM DIMENSION
DN DOWN
D.O. DOOR
DTL DETAIL
DWG DRAWING
E EXISTING
ELEC ELECTRIC
ELEV ELEVATION
EQUIP EQUIPMENT
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FB FIAT BAR
FH FLAT HEAD
FIN FINISH(ED)
FLR FLOOR
FOS FACE OF STUDS
FS FINISH SURFACE
FT FOOT, FEET
FTG FOOTING
FIN FINISH WALL
VCT VINYL
COMPOSITION
NIC NOT IN CONTRACT TILE
NO NUMBER VERT VERTICAL
NTS NOT TO SCALE VG VERTICAL GRAIN
OA OVERALL W/ WITH
OC ON CENTER WC WATER CLOSET
OPNG OPENING WD WOOD
OPP OPPOSITE W/H WATER HEATER
WATER RESISTANT
P P ITION Wi WEIGHT
PLAS PLASTER
PLASLAM PLASTIC LAMINATE
PLYWD PLYWOOD
POC POINT OF CONNECTION
PROP PROPERTY
O AT
C CHANNEL
fL CENTERUNE
• ANGLE
veri
5295 S. 300 W. SUITE 175
MURRAY, UT. 84107
APPROVALS
*EDMONDS
OPLANO
HINCKLEY
HIBBARD
'
SALEM
ARK
HORNTON
ORENZO 'MAN
° LABELLE
R
nVVireless
HART o TETON a NEWDALE
UGAR CITY
BURG SITE
° JENSEN
'8IALKER
° GALE
° ARCHER
,BYRNE
SUNNYDELL
VICINITY MAP
N.T.S.
MILFORD
WOODS
CROSSING
PROJECT MANAGER Data
PROPERTY MANAGER Data
RF ENGINEER Data
CONSTRUCTION MANAGER Date
NO. DATE
REVISION BY CHKO APVLS
07
12 ISSUED FOR VERIZON REVIEW
02
814 JAP MAN
0
A
No110538
J , 1 IT- A -ZI@,
verTZPO
Wireless
cti
MERICOM
C O R P O R A T I O N
Utah Market Office
429 Lawndale Drive
Salt Lake City, UT 84115
Tel: 801 486.3171
Fax: 801.486.0858
Central West Regional Office
4700 Northgate Blvd., Suite 160
Sacramento, CA 95834
Tel: 916.4703990
Fax: 916.920.2343
SITE INFORMATION
ID6 REXBURG
NW 1/4 OF SEC. 33, T6N, R40E, B.M.,
MADISON COUNTY, IDAHO
DESIGN TYPE
DIESEL GENERATOR
SHEET TITLE
TITLE SHEET
SHEET NUMBER REV.
T -1
A
DWG NAME: T1
DATE: 07.10.02
50' -0"
EXISTING POWER
RACK /DISCONNECT
EXISTING CHAIN LINK
FENCE
NOTE:
DRAWINGS CREATED FROM FIELD
MEASUREMENTS, CONTRACTORS
SHOULD VERIFY ALL DISTANCES.
L ,
1
PROPOSED
GENERATOR
HVAC
GENERATOR
ROOM
EXISTING VERIZON
12' -0" X 28' -0'
EQUIPMENT SHELTER
HVAC
50' 0"
PROPOSED ATS
REMOVE APPLETON
PLUG
O ENLARGED SITE PLAN
SCALE : 1/4" a 1' -0"
EXISTING PROPANE 65 - FUEL LINE
EXISTING PROPANE TANK
15.9"
N0.
0
0
DATE
07
12
02
REVISION
ISSUED FOR VERIZON REVIEW
Br
CHKD
JAP
SHEET NUMBER
E -1
APVIS
Verr
VVireless
MERICOM
C O R P O R A T I O N
Utah Market Office
429 Lawndale Drive
Salt Lake City, UT 84115
Tel: 801.486.3171
Fax: 801.486.0858
Central West Regional Office
4700 Northgate Blvd., Suite 160
Sacramento, CA 95834
Tel: 916.470.7990
Fax: 916.920.2343
SITE INFORMATION
106 REXBURG
NW 1/4 OF SEC. 33, TBN, R40E, B.M.,
MADISON COUNTY, IDAHO
DESIGN TYPE
DIESEL GENERATOR
SHEET TITLE
ENLARGED SITE PLAN
REV.
A
DWG NAME: E1 I DATE: 07.10.02
PROPOSED 2 1/2" C,
(3) #4, (1) #8 EGC
PROPOSED 1/2" C, POWER TO NEW ATS
(2) #16, GENERATOR
CONTROL CONDUCTORS
PROPOSED
GENERAC SGO60
GENERATOR
PROPOSED 2 -1/2" C,
(3) #4/0, (1) #2 EGC
PROPOSED 3/4" C, (2) #12,
(1) #12 EGC, BATTERY CHARGER
AND HEATER CONDUCTORS
PROPOSED 200A, 120/240V
1 PH ATS ON EXTERIOR WALL
OF BUILDING
PROPOSED 2- 1 /2 "C,
(3) #4/0 (1) #2 EGC
EXISTING 200A, 120/240V,
1PH PANEL BOARD
300
VERZON SHELTER OI -U E DIAGRAM
EXISTING 200A, 120/240V
1 PH FUSIBLE DISCONNECT
ON THE EXTERIOR WALL OF
THE BUILDING
o\
ET
� SURGE
ARRESTER]
1
1
ATS: AUTOMATIC TRANSFER SWITCH
REMOVE
CONDUCTORS
INSTALL 120V, 20A CB FOR
GENERATOR BATTERY CHARGER
AND HEATER IN AVAILABLE
SPACE
EGC: EQUIPMENT GROUNDING CONDUCTOR
7 EXISTING 200A 120/240V 1PH
METER ON EXTERIOR WALL OF
BUILDING
l
EXISTING
BUILDING
-L
CTRICAL \OT
=S:
1. EXTERIOR GROUNDING SYSTEM BY THE ELECTRICAL CONTRACTOR.
2. BENDS FOR GROUND WIRES WILL BE 12" RADIUS OR GREATER
3. DO NOT ROUTE GROUNDING THROUGH EMT CONDUIT
4. GROUND WIRES TO "FLOW" TO MASTER GROUND BAR
5. ALL GROUND WIRES TO BE INSULATED GREEN STRANDED COPPER THHN
6. ALL GROUND WIRES INSTALLED TO MASTER GROUND BAR TO BE TAGGED
TO INDICATED ORIGIN AND SAY "DO NOT DISCONNECT"
7. ALL GROUNDING WIRES TO BE CONNECTED TO MASTER GROUND BAR
WITH TWO HOLE LUGS
8. USE ANTI CORROSIVE COMPOUND ON ALL CONNECTIONS AND BE
CLEANED PRIOR TO CONNECTING
9. NO SPLICING OF GROUND WIRES
10. ALL WIRING PER NEC AND LOCAL CODES
11. MULTIPLE GROUND WIRES NOT ALLOWED ON SAME BOLT UNLESS
ON OPPOSITE SIDE OF MASTER GROUND BAR
12. TORQUE PER SAE STANDARD
13. LUGS TO MAKE G000 CONTACT WITH EQUIPMENT, STAR WASHERS
ARE PROHIBITED
14. IF HEAT SHRINK LABELS ARE USED POSITION FOR CLEAR VIEWING
15. PROVIDE BONDING CONNECTIONS BETWEEN ALL EXTERIOR METALLIC
OBJECTS TO EXTERIOR GROUND RING
NO.
0
A
0
0
A
DATE
07
12
02
REVISION
ISSUED F00 VERQON RMEW
BY
88
SHEET NUMBER
E -2
CHKD
dW
APVLS
1WJ
Wireless
MERICOM
C O R P O R A T I O N
Utah Market Office
429 Lawndale Drive
Salt Lake City, UT 84115
Tel: 801.486.3171
Fax: 801.486.0858
Central West Regional Office
4700 Northgate Blvd., Suite 160
Sacramento, CA 95834
Tel: 916.470.7990
Fax: 916.920.2343
SITE INFORMATION
ID6 REXBURG
NW 1/4 OF SEC. 33, TUN, R40E, ELM.,
MADISON COUNTY, IDAHO
DESIGN TYPE
DIESEL GENERATOR
SHEET TITLE
ONE -LINE DIAGRAM
REV.
A
DWG NAME: E2 l DATE: 07.10.02
48
APPROX.
FIELD VERIFY
DURINE OF GENERATOR
NO
DATE
REVISION
BY
CHKD
APVL.S
07
12
D2
ISSUED FOR VERQON REVIEW
BM
,lAP
WN
.
^gp
t
r - - - 1
1
1
1 1
I
L - - -J
A
0
Q
,_ - �
1
1
CHAMFER CORNER 1
3/4" TYPICAL I ._
�_�
V
EMERGENCY
W/
LONG
6
_ �
I
I
I
6 -5/0
ANCHOR
GENERATOR
X 12"
BOLTS
z
m
Q
O, ��^
\ �Si£
TY ;,
v t...t , 0
. -. �
blerf Ong
E 12 -2 -280
� q 1 [If ��
�/ A C. GON --
. .
T.O. FINISHED GRADE
CONCRETE PAD W/ +5.12" O.C.
EA. WAY. HOOK ALL ENDS D OWN
14" TYPICAL
I
1/2" CLR TYP
611
GENERATOR FOUNDATION SECTION WILE MTS.
ALL SITE WORK SHALL BE AS INDICATED ON THE DRAWINGS AND STIPULATED IN
THE PROJECT SUMMARY.
2. RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER REFUSE SHALL BE
REMOVED FROM THE SITE AND DISPOSED OF LEGALLY.
3. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM
THE PCS EQUIPMENT, TOWER AREAS, AND ADJACENT BUILDINGS
4. THE SUB GRADE SHALL 8E COMPACTED AND BROUGHT TO A SMOOTH UNIFORM
GRADE PRIOR TO THE CRUSHED STONE APPLICATION.
5. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES WHERE
ENCOUNTERED IN THE WORK, SHALL BE PROTECTED AT ALL TIMES, AND WHERE
REQUIRED FOR THE PROPER EXECUTION OF THE WORK, SHALL BE RELOCATED AS
DIRECTED BY ENGINEERS. EXTREME CAUTION SHOULD BE USED BY THE
CONTRACTOR WHEN EXCAVATING OR PIER DRILLING AROUND OR NEAR UTILITIES.
CONTRACTOR SHALL PROVIDE SAFETY TRAINING FOR THE WORKING CREW.
6. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES,
WHICH INTERFERE WITH THE EXECUTION OF THE WORK, SHALL BE REMOVED AND
SHALL BE CAPPED, PLUGGED OR OTHERWISE DISCONTINUED AT POINTS WHICH
WILL NOT INTERFERE WITH THE EXECUTION OF THE WORK, SUBJECT TO THE
APPROVAL OF ENGINEERING.
7• THE AREAS OF THE CUSTOMER'S PROPERTY DISTURBED BY THE WORK AND NOT
COVERED BY THE BUILDING, DRIVEWAY OR CRUSHED STONE, SHALL BE GRADED
TO A UNIFORM SLOPE, FERTILIZED, SEEDED, AND COVERED WITH MULCH.
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301, ACI 318.
2. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 2000 PSI
AT 28 DAYS UNLESS NOTED OTHERWISE.
3. REINFORCING STEEL SHALL CONFORM TO ASTM A 615, GRADE 60, DEFORMED
UNLESS NOTED OTHERWISE. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A
185 WELDED STEEL WIRE FABRIC UNLESS NOTED OTHERWISE. SPLICES CLASS
"g" AND ALL HOOKS SHALL BE STANDARD UNO.
4. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR
REINFORCING STEEL UNLESS SHOWN OTHERWISE ON DRAWINGS:
CONCRETE CAST AGAINST EARTH 3 IN.
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 AND LARGER 2 IN. #5 AND
SMALLER & WWF 1 1/2 IN.
CONCRETE NOT EXPOSED TO EARTH OR WEATHER OR NOT CAST AGAINST THE
GROUND:
SLAB AND WALL 3/4 IN. BEAMS
AND COLUMNS 1 1/2 IN.
5. A 1/2" TRAWLED RADIUS SHALL BE PROVIDED AT ALL EXPOSED EDGES OF
CONCRETE UNO.
6. HOLES TO RECEIVE EXPANSION /WEDGE ANCHORS SHALL BE 1/8" LARGER IN
DIAMETER THAN THE ANCHOR BOLT, DOWEL OR ROD AND SHALL CONFORM TO
MFR. RECOMMENDATION FOR EMBODIMENT DEPTH OR AS SHOWN ON THE
DRAWINGS. AVOID CUTTING EXISTING REBAR WHEN DRILLING HOLES IN THE
ELEVATED SLAB.
7. INSTALLATION OF CONCRETE EXPANSION /WEDGE ANCHOR, SHALL BE PER
MANUFACTURER'S WRITTEN RECOMMENDED PROCEDURES.
8. FLOAT SURFACE SHALL BE A SMOOTH FINISH. SURFACE SHALL BE FREE OF ALL
OBVIOUS DEPRESSIONS. SURFACE SHALL BE LEVEL TO WITHIN ± 1'. SURFACE
FLATNESS SHALL BE ± 1/16" PER YARD.
\'''''.°.
. Wire %ss
9 7"
3' 10"
4'_8"
4 _g
=
- _ = 1r,
- - -
,;
1,
GENERATOR
4
8"
1
-
1' -10"
,1 I,
1
M E R I C i M
C O R P O R A T I O N
7' g°
LEFT SIDE VIEW
3' 6" --I
REALM
NOTES:
1. DETAILS SHOWN FOR ILLUSTRATIVE PURPOSES ONLY REFER
TO MANUFACTURER'S DRAWINGS.
WEIGHT: UNIT 1843 LBS.
STEEL CABINET 600 LBS. 2. FOR FOUNDATION/ CONCRETE SLAB REFER TO MANUFACTURER'S
DRAWINGS.
Utah Market Office Central West Regional Office
429 Lawndale Drive 4700 Northgate Blvd., Suite 160
Salt Lake City, UT 84115 Sacramento, CA 95834
Tel: 801.486.3171 Tel: 916.470.7990
Fax: 801.486.0858 Fax: 916.920.2343
500
1
����
L>CI�CRAC 80080/120/240V
STANDARD C NOTES SCALE: N.T.S.
1 DIESEL GENERATOR scut: N.Y.S.
•
SITE INFORMATION
ID6 REXBURG
NW 1/4 OF SEC. 33, T6N, R40E, B.M.,
MADISON COUNTY IDAHO
DESIGN TYPE
DIESEL GENERATOR
SHEET TITLE
DETAILS
SHEET NUMBER
REV.
E -3
505
505
CONC. AND REINFORCED BAR NOTES SCALE: N.T.S.
DWG NAME: E3 I DATE: 07.10.02