HomeMy WebLinkAboutCO & DOCS - 02-00012 - Dr Christensen Doctors' OfficeOccupancy:
CERTIFICATE OF OCCUPANCY
City of Rexburg
Department of Building Inspection
Building Permit No. R- o2 -o4 -11
Building Street Address: 370 East 1st South
Building Owner: Dr. Brian Christensen
Contractor: Harold L. Harris Construction
Description of building or portion of building for which this certificate is
issued:
Date: 09 -25 -2002
C.O. Issued by:
Commercial - Doctors' Offices
Full
Tbis Certificate, issued rsuant to the requirements of Section 109 of tbe Uniform Buntline
Cote, certifies that, at t e time of issuance, this bui[ain9 or that portion of tbe bui[r)in that
9
was inspected on the Gate Lister) was f ouno to be in compliance with the requirements of the
code for the group and division of occupancy and the use for wbich the proposer) occupancy
was cLassi f ier).
Building Official
There shall be no future change in the existing occupancy classification of the building nor shall
any structural changes, modifications or additions be made to the building or any portion thereof
until the Buildg Offi 'al has revie d and approved said future changes.
Water Department Department
State of Idaho Electrical Department - (208 - 356-4830) 0
vnncn a . !�`: d" ✓"� �;: d * f _ � A " ' . :,rM .RJC AWHt.1, o
�, p.
q�''t(4 S <. d ► }�t�' , .r + +t.,fik PHONE
f
BUILDER r r :p , ; h . ;e ,,'.- , ARCHITECT
DESIGNER „v x ± 3 :; r " '` W ,
STRUCTURE: I3IEW O REMODEL 0 ADDITION
0 REPAIR 0 RENEWAL O FIRE DAMAGE
0 RESIDENCE 11COMM. O EDUCATIONAL O GOVT 0 RELIGIOUS
0 FENCE 0 PATIO 0 CARPORT O GARAGE 0 AWNING
FOOTINGS
FOUNDATION
BASEMENT
FLOORS
EXT. WALLS
I . WALLS
CEIUNG
ROOF
HEAT
INSULATED
(*CONCRETE
O MASONRY
0 OTHER
CtCONCRETE
0 MASONRY
0 OTHER
O PARTIAL
❑FULL
U NO
I�] WOOD
CONCRETE
0 OTHER
(WOOD
0 MASONRY
0 CONCRETE
tikVENEER
0 METAL
0 STUCCO
0 MOD
0 ONRY
0 CRETE
apRYWALL
O PLASTER
0 ILE
Q WOOD
CI DRYWALL
O PLASTER
0 TILE
O ACOUSTIC
0 OPEN40
0 MILT UP
0 WOOD SH.
EiCOMP. SH.
0 TILE
0 ROLL ROOF.
0 METAL
f GAS
0 OIL
0 COAL
0 FIREPLACE
0 ELECTRIC
CYWALLS
1° CEILIN
0 FL
1XPERi ER
a
f*
This permit is issued subject to the regulations contained in the Uniform Building Code and Zoning Regulations of Rexburg, and it is hereby agral
that the work to be done as shown in the plans and specifications will be completed in accordance with the regulations
pertaining and applicablb thereto: The issuance of the permit does not wane restrictive covenants.
BUILDING PERMIT APPLICATION REXBURG, ID DATE NO..
THE UNDERSIGNED HEREBY APPLIES FOR A PERMIT FOR THE WORK HEREIN INDICATED
OR AS SHOWN AND APPROVED IN THE ACCOMPANYING PLANS AND SPECIFICATIONS,
dt
ITY. OF
1
APR 1 'r 2002
REMARKS:
DEPARTMENT OF BUILDING & ZONING
VALUE
FEE PAID
BUILDING
INSPECTOR
WHITE- Owner's Copy CANARY- Building Departments Copy PINK- Assessors C
GOLDENROD- Inspector
Date of Application 3 - / e•0 Z
OWNER
Name /i Rykr Ch )01'5 TEA/ SEicl
APPLICATION FOR BUILDING PERMIT
CITY OF REXBURG, IDAHO
Site Address 37 E. l S r S' , Zv M <1A <5 ON Pe0FitZ 5/ 0,mL _
Mailing Address 3 0' ‘ (•O 77emeLooeDL L�
City / State/Zip P., b ?3 f0
Telephone/Fax/Mobile ZS - L — to Sal b F f F 6 S g/
CONTRACTOR
Name 7 L • c' a A-JS T•
Mailing Address n U ?D - 30
City /State/Zip Sv ,6/4-2 G r 2. ?3 Y' 2
Telephone/Fax/Mobile ?56 - 3 3 - 356 ?0,3
PROJECT INFORMATION DEPARTMENT APPROVAL
Property Zone: Is existing use compatible with zoning, (screening parking, etc)
When was this building last occupied
Architect/ Engineer Firm er - 4 . Plan Name
Subdivision MAt1>/s o P�ofES s fdn / fste. Lot
Circle One New House
Circle One Basemen
Lot Square Footage /(570
Signature of Applicant
Code
Zone
Building Type
Addition/Remodel to House
Square Feet 24, Garage Square Feet
What will structure be used for:
Will there be an apartment? 416
Total Estimated Cost # 2 2
Lot Width
76 '
* * * * * * * * * * * * * * * * * * * * * * * * * * * * ** r * * * * * * * * * **
Are you in a flood plain
Plan Check Fe
Plumbing Permi
Digging Permit
Permit No. k 42? -eo -//
Circle One Residential(ommercial Educational Government Remodel Other
(New Commercial) Commercial Remodel
Finished / Unfinished Other: None/ Patio/ Carport/ Awning N/A
Number of Stories / Height of Building l 7 "
Home Home Business Apartment CConimercial� Other
If so, how many units
A/D
************************ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
Building Permi 'Fees
Water & Sewer Fees
Block
'`e0"Z`I TOTAL $
Signature of Inspector G'■/
Issued by
Rough Plumbing
Septic Tank
Fixtures
Water Piping
Complete
Sewer
Bath Tubs
Urinal
Showers
Sink Trap
Laundry Trays
Water Heater
Wash Basin
Other
Toilet
Slop Sinks
Kitchen Sinks
Floor Drain
Drinking Fountains
Lawn Sprinklers
Water Softeners
Dish Washing Mach.
Clothes Washer
OWNER
Address r " - �- r Tel.
Lot Blk. add.
Name
Name 1 {. ,h
PLUMBER
Address Tel.
NATURE OF INSTALLATION
Use
DESCRIPTION OF WORK
CITY OF REXBURG
APPLICATION FOR PLUMBING PERMIT
FEES
Plumbing Permit $
Sewer Inspection $
Inspection of Pipe $
Inspection of Fixtures
Rough PI u bing
Sewer
Other
Finish Plumbing
TOTAL $
Received: Date
By fed •
PAIO
INSPECTOR'S RECOR
N
APR 1 7 2002
C TY OF FFXBiiRt
s
E
INSP. NAME
Excavation &
Ccncreto: cis R - .0
Mascnry : E MWS6AJ e
Roofing: G N I2 C` ()NTe
Insulation: a1 L
Drywall :
Painting : • c 4$4:›
Floor Coverings: LJ& NCrt-t.) (A-)
Plumbing:
Heating:
E? ectrical : E / 5 /9772/410
Roof Trusses: -�
Floor / Ceiling Joists:
Cabinets:
Siding /Exterior Trim:
Cther:
SUBCONTRACTOR LIST
SPECIAL CONSTRUCTION
(MANUFACTURER OR SUPPLIER)
Project Number: 02_06
Project Name: Dr. Christensen
Address: 370 East 1st South
Occupancy: B
Construction: V -N
CITY OF REXBURG
ENGINEERING
12 NORTH CENTER
REXBURG, IDAHO 83440
(208)359 -3020
Plan analysis based on
the 1997 Uniform Building Code
Date: March 14, 2002
Contractor: Harris
Architect:
Engineer: Woolstenhulme
Report By: VAL CHRISTENSEN
NOTE: The code items listed in this report are not intended to be a
complete listing of all possible code requirements in the 1997 UBC.
It is a guide to selected sections of the code.
Report created using Plan Analyst software by b w & a. (719) 599 -5622
Portions of the material contained in this program are reproduced
from the Uniform Building Code with the permission of the
International Conference of Building Officials.
SEPARATION
DIRECTION BOUNDARY AREA INCREASE FIRE PROTECTION
NORTH Property line 10.5 Feet 10.5 Feet
EAST Public way 117.0 Feet 67.0 Feet
SOUTH Property line 10.5 Feet 10.5 Feet
WEST Property line 21.7 Feet 21.7 Feet
Allowable area increased 2.09% for open area on 2 sides.
-- Sec. 505.1
FL
NAME OCC MAX FLR AREA ALLOWED RATIO STATUS
1 Office B ok 2600 8167 0.32 ok
TOTAL FOR FLOOR 2600 8167 0.32 ok
BUILDING TOTAL 2600 8167 0.32 ok
-- Sec. 504 and Table 5 -B
The actual height of this building is 25. feet.
The maximum height of the building is 40. feet. -- Table 5 -B
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
Page # 2
EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION
Table 5 -A
NORTH
For Bearing Non - Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
B 1 hour 1 hour None Any No
EAST
For Bearing Non - Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
B 0 hour 0 hour None Any No
SOUTH
For Bearing Non - Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
B 1 hour 1 hour None Any No
WEST
For Bearing Non - Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
B 0 hour 0 hour None Any No
None -- No fire protection requirements for openings.
3/4 hour -- Openings are to be protected with 3/4 hr fire assemblies.
50% of the area of the wall maximum. -- Table 5 -A,
Footnote 5 & Sec. 503.2.2
Maximum single window size is 84 sq.ft. with no dimension
greater than 12 feet. -- Sec. 713.8
Not Allowed -- Openings are not permitted in this wall.
OTHER BUILDING ELEMENTS Table 6 -A
ELEMENT MATERIAL RATING NOTES
Interior Bearing wall Any 0 hr
Interior nonbrg wall Any 0 hr See Footnote #5
Structural Frame Any 0 hr
Exterior Struct Frame Any 0 hr See footnote #1
Floor /Ceiling Assembly Any 0 hr
Roof /Ceiling Assembly Any 0 hr See Footnote #8
Stairs Any None
FOOTNOTES:
1) Elements in an exterior wall located where openings are not permitted
or where protection of openings is required, shall be protected
against external fire exposure as required for exterior bearing walls
or the structural frame, whichever is greater. -- Table 6 -A, footnote 1
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
Page # 3
PENETRATIONS OF FIRERESISTIVE ASSEMBLIES
WALLS ASSEMBLIES Sec. 709.6
Through penetrations:
1) Penetrations shall be installed as tested in the rated assembly.
-- Sec. 709.6.2
2) Penetrations shall be protected by an approved penetration
firestop system and shall have an F rating of not less than the
required rating of the wall penetrated. -- Sec. 709.6.3
Exception: When penetrating items are steel, ferrous or copper
pipes or steel conduits and the wall is concrete or
masonry, the annular space shall be permitted to be
grout or mortar. The minimum thickness is the
thickness required to maintain the fire rating. The
maximum size of the penetrating items is equivalent
to a 6 -inch diameter and the opening is a maximum of
144 square inches. -- Sec. 709.6.1
Membrane penetrations:
The requirements are the same as for through penetrations.
-- Sec. 709.7
Exceptions:
1. Steel electrical outlet boxes that do not exceed 16 square
inches provided that the area of such openings does not exceed
100 square inches for any 100 square feet of wall area.
Boxes on opposite sides of the assembly shall be
separated by a horizontal distance of not less than 24
inches.
2. Sprinklers with metal escutcheon plates.
Noncombustible penetrating items shall not be connected to
combustible materials on both sides of the membrane unless it can
be confirmed that the fire - resistive integrity of wall is
maintained. -- Sec. 709.7
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
Page # 4
FLOOR /CEILING AND ROOF /CEILING ASSEMBLIES -- Sec. 710.2
Through pentrations:
Through penetrations of fire - resistive horizontal assemblies shall
be enclosed in fire - resistive shaft enclosures. -- Sec. 710.2.1
Exceptions:
1. When penetrating items are steel, ferrous or copper conduits,
pipes, tubes and vents through a single concrete floor, the
annular space shall be permitted to be grout or mortar.
The minimum thickness is the thickness required to maintain
the fire rating. The maximum size of the penetrating items is
equivalent to a 6 -inch diameter and the opening is a maximum
of 144 square inches.
2. Electrical outlet boxes that have been tested for use in
fire - assemblies.
The system shall have an F rating and a T rating of not less than
one hour but not less than the required rating of the floor system.
-- Sec. 710.2.3
Exception: Floor penetrations contained and located within the
cavity of a wall do not require a T rating.
Membrane penetrations:
The requirements are the same as for through penetrations.
-- Sec. 710.3
Exceptions:
1. When penetrating items are steel, ferrous or copper
conduits, electrical outlet boxes, pipes, tubes and vents
through concrete or masonry and the annular space is
protected by an approved penetration firestop assembly or
protected to prevent the free passage of flame and
products of combustion. Such penetrations shall not
exceed an aggregate area of 100 square inches in any 100
square feet of ceiling area in assemblies without
penetrations.
2. Electrical outlet boxes that have been tested for use in
fire - assemblies.
3. Sprinklers with metal escutcheon plates.
Fire - resistive roofs may have unprotected openings. -- Sec. 710.4
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
Page # 5
SMOKE and FIRE DAMPERS -- Sec. 713.10 and 713.11
Dampers shall be accessible for inspection and servicing:
1. Penetrations through area separation walls.
Penetrations through occupancy separations.
2. Penetrations of the fire- resistive construction of horizontal
exit walls or corridors serving as a means of egress.
Exception: Openings for steel ducts penetrating the required
fire - resistive construction of corridors are not
required to have smoke dampers when such ducts
are of not less than 0.019 -inch thickness
(26 gage) and have no openings serving the
corridor.
3. Penetrations of shaft enclosures.
Exceptions:
1. Duct penetrations by steel exhaust air subducts
extending vertically upward at least 22 inches above
the top of the opening in a vented shaft where the
airflow is upward.
2. Penetrations of a fire - resistive floor forming the
base of a shaft enclosure may be protected by fire
dampers listed for installation in the horizontal
position.
3. Smoke dampers are not required when shaft is exhaust
only, and is used for continuously operating fans.
4. Penetrations of the ceiling of fire - resistive floor- ceiling
or roof - ceiling assemblies.
Exception: Smoke dampers are not required.
5. Penetrations of an atrium enclosure element.
Exception: Smoke dampers are not required.
6. Penetrations of exterior walls where protection of openings
is required.
Exception: Smoke dampers are not required.
7. Penetrations of areas of refuge.
Exception: Ventilation system designed to supply outside
air during an emergency.
8. Smoke dampers are required in smoke barriers and elevator
lobbies.
DRAFT STOPS:
If there is combustible construction in the roof /ceiling assembly, draft
stops shall be installed so that the area of concealed space does not
exceed 3,000 square feet and so that the horizontal dimension between
stops does not exceed 60 feet. -- Sec. 708.3.1.2.2
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
1 Office
TOTAL
FOOTNOTES:
Page # 6
EXIT REQUIREMENTS:
FL NAME NUMB MIN MIN PANIC HALLWAY/ DOOR NOTES
OCC EXITS WIDTH HDWR CORRIDOR SWING
26 1 5.2 No N/A N/R
26 1 5.2 No N/A N/R
Door swing is based on Sec. 1003.3.1.5 except as noted.
Occupant load factor is based on Table 10 -A.
Number of exits is based on Table 10 -A except as noted.
Exit width is in inches and based on Sec. 1003.2.3 and Table 10 -B
Exit width is to be divided approximately equally among exits.
-- Sec. 1003.2.3.2
Width shown for all areas is based on other egress components.
Width shown for 1st floor is based on other egress components.
Width shown for other floors & basements is based on stairways.
-- Table 10 -B
For the minimum width of doors, see Sec. 1003.3.1.3
For the minimum width of hallways, see Sec. 1004.3.3.2
For the minimum width of corridors, see Sec. 1004.3.4.2
For the minimum width of stairways, see Sec. 1003.3.3.2
FLUSH AND SURFACE BOLTS:
Manually operated edge- or surface - mounted flush bolts and surface
bolts or any other type of device that may be used to close or
restrain the the door other than by operation of the locking device
shall not be used. When automatic flush bolts are used, the door
leaf having the automatic flush bolt shall not have a door knob or
surface - mounted hardware. The unlatching of any leaf shall not
require more than one operation. -- Sec. 1003.3.1.8
LOCKS AND LATCHES:
Regardless of the occupant load served, exit doors shall be openable
from the inside without the use of a key or any special knowledge or
effort. -- Sec. 1003.3.1.8
Key - locking hardware may be used on the main exit when the main exit
consists of a single door or pair of doors if there is a sign stating
THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS. When unlocked,
door(s) must swing without operation of any latching device. -- exc.
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
Page # 7
LANDINGS AT DOORS:
1) A floor or landing shall be provided on each side of doors. When
access for persons with disabilities is required. the floor or landing
shall not be more than 1/2 inch lower than the threshold. When access
is not required, the maximum is 1 inch. -- Sec. 1003.3.1.6
2) Landings shall have a width not less than the width of the stairway
or width of the doorway, whichever is the greater. Where a landing
serves an occupant load of 50 or more, doors in any position shall
not reduce the landing dimension to less than one half it required
width. The minimum length in the direction of exit travel is 44 inches.
-- Sec. 1003.3.1.7
TRAVEL DISTANCE: (distance to an exit)
The maximum travel distance in this building is 200 feet. -- Sec. 1004.2.5.2.1
Travel distance shall not be limited within an exit enclosure or exit
passageway. -- Sec. 1005.2.2
BUILDING ACCESSIBILITY:
In offices (except health -care providers) and retail sales floors,
with an aggregate area of not more than 3000 above or below the
accessible floor need not be accessible. -- Sec. 1103.2.2 Exception
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
Page # 8
1) This building including each tenant shall be provided with at least
one entrance which complies with the accessible route provisions of
CABO /ANSI A117.1. At least 50 percent of all entrances shall be
accessible. -- Sec. 1103.2.3
2) When more that one exit is required from any accessible space, each
accessible portion of the space shall be served by not less than two
accessible means of egress. -- Sec. 1104.1.1
3) When an exit stairway is part of an accessible means of egress, the
stairway shall have a clear width of not less than 48 inches between
the handrails. The stairway shall either incorporate an area of refuge
within an enlarged story -level landing or shall be accessed from
an area of refuge. -- Sec. 1104.1.2
The area of refuge shall have direct access to the stairway that serves
it. -- Sec. 1104.2.1
4) Each area of refuge shall be sized to accommodate one wheelchair space
not less than 30 inches by 48 inches for each 200 occupants, or
portion thereof. -- Sec. 1104.2.3
5) If the area of refuge is not within the stairway, it shall be separated
from the rest of the story by a smoke barrier having at least a one -
hour fire- resistance rating. Smoke barriers shall extend to the roof or
floor deck above. Doors shall be smoke and draft control assemblies
with a rating not less than 20 minutes. -- Sec. 1104.2.4
6) Two -way communications are required. -- Sec. 1104.2.5
7) Each area must be identified by a sign stating AREA OF REFUGE and the
international symbol of accessibility. -- Sec. 1104.2.7
8) NOTE: Exit stairways in buildings protected throughout by an approved
automatic sprinkler system are NOT required to incorporate an area of
refuge. -- Sec. 1104.1.2, Exception 2
ROOFING REQUIREMENTS:
1) The roofing on this building is required to be Class C. -- Table 15 -A
2) See section 1504 and ICBO research reports for requirements.
AUTOMATIC SPRINKLER SYSTEMS:
If openings are not provided in each 50 feet of exterior wall or there
is floor area more than 75 feet from an exterior opening, an automatic
sprinkler system is required. -- Sec. 904.2.2 Note: Openings shall have
a minimum dimension of 30 inches. There must be at least 20 sq.ft. of
opening in every 50 lineal feet of wall.
STANDPIPE REQUIREMENTS:
There is no requirement for a standpipe. -- Table 9 -A
FOOTNOTES:
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
ADDITIONAL REQUIREMENTS:
For B occupancy
Page # 9
VENTILATION:
All areas customarily occupied by humans shall be provided with natural
ventilation by means of openable exterior openings with an area of not
less than 1/20 of the total floor area or shall be provided with a
mechanically operated ventilation system. Such system shall be capable
of supplying a minimum of 15 cubic feet per minute of outside air per
occupant. -- Sec. 1202.2.1
WALL AND CEILING FINISH:
1) Wall and ceiling finish materials are required to comply with
Sec. 804.1 and Table 8 -B.
2) Carpeting on the ceiling is required to have a Class I flame
spread rating. -- Sec. 804.2
3) Textile wall coverings shall have Class I flame spread rating.
and shall be protected by automatic sprinklers or meet the
acceptance criteria of U.B.C. Standard No. 8 -2 -- Sec. 805
4) Toilet room floors shall have a smooth, hard nonabsorbent surface
that extends upward onto the walls at least 5 inches.
-- Sec. 807.1.1
5) Walls within 2 feet of the front and sides of urinals and water
closets shall have a smooth, hard nonabsorbent surface.
-- Sec. 807.1.2
INSULATION NOTES:
1) All insulation material including facings are required to have a
flame - spread rating of 25 or less and a maximum smoke density of 450
unless it is in a concealed space and the facing is in contact with
a wall or ceiling. -- Sec. 707.3 exc.2
2) Foam plastic insulations are required to be protected. -- Sec. 2602
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
Page # 10
ACCESSIBLE FACILITIES:
NOTE: Except as noted, section numbers listed below are from
CABO /ANSI A117.1 - 1992
WATER FOUNTAINS AND WATER COOLERS:
At least 50 percent of drinking fountains, but not less than one,
provided on every floor shall be accessible. -- UBC Sec. 1105.4.1
Accessible units must comply with the following:
1) Spout is to be within 36 inches of the floor. -- Sec. 4.15.2.1
2) Spout arranged for parallel approach shall be located 3 inches
maximum from the front edge. Spouts of cantilevered units with
knee and toe clearances shall be located 15 inches minimum from
the vertical support and 5 inches maximum from the front edge.
-- Sec. 4.15.2.2
3) Spouts shall provide a flow of water 4 inches height minimum.
-- Sec. 4.15.2.3
4) Operable parts shall be located at or near the front edge of the
unit and shall comply with 4.25.4 -- Sec. 4.15.3
5) A cantilevered unit is required to extend 17 inches minimum from
the vertical support. Clear knee space must provide a clear area
of 8 inches in depth at 27 inches high and 11 inches at 9 inches
minimum above the floor. -- Sec. 4.15.4.1
6) Forward approach units shall comply with 4.2. Units in alcoves
shall comply with 4.2.4.4. Units not having the necessary knee
and toe clearance or clear space under them shall comply with
4.2.4 and have a clear floor space that allows a person in a
wheelchair to make a parallel approach. -- Sec. 4.15.4.2
TOILET FACILITIES:
1) A 60 inch diameter unobstructed turning space is required in
the toilet room. -- Sec. 4.16.3, 4.2.3 & Fig. B4.2.3
2) Water closet shall be mounted adjacent to a side wall or
partition. The distance from the side wall or partition to the
centerline of the water closet shall be 18 in. Sec. 4.17.1
3) When the accessible water closet is not in a stall:
The clear floor space shall be 48 in minimum in front
of the water closet and 42 in from the center line of the
water closet on the side not adjacent to the wall.
-- Sec. 4.17.2 & Fig. B4.17.2
4) When the accessible water closet is in a stall:
The stall shall be 60 in wide minimum and 56 in deep minimum
for wall hung water closets and 59 in deep minimum for floor
mounted water closets. -- Sec. 4.18.3.1
If the door swings into the stall, the required depth shall
be increased by 36 inches minimum. -- Sec. 4.18.3.2 &
Fig. B4.18.3.1
5) The bars are to be 33 to 36 inches above the floor and shall
be provided on the rear wall and on the side wall closest to
the water closet. -- Sec. 4.24.2.2 & Figs. B4.17.3, B4.17.4
and B4.18.3.1
a) Side grab bar is required to start within 12 inches of the
back wall and extend to 54 inches from the back wall. (The
minimum length of the bar is 42 in) -- Sec. 4.17.4.1 &
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
Page # 11
Figs. B4.17.3 and B4.18.3.1
b) The rear bar shall be 24 in long minimum, centered on the
water closet. Where space permits, the bar shall be 36 in
long minimum, with the additional length provided on the
transfer side. -- Sec. 4.17.4.2 & Figs. B4.17.3, B4.17.4
and B4.18.3.1
6) The top of the seat on the water closet is required to be 17
to 19 inches above the floor. -- Sec. 4.17.3 & Fig. B4.17.3
7) Accessible urinals shall be of the stall type or wall hung with
the rim at 17 inches maximum above the floor. -- Sec. 4.19.2
8) A clear area of 30 X 48 inches minimum is required in front
of the urinal. Privacy shields shall not extend beyond the
front edge of the urinal rim, unless they are 30 inches apart
minimum. -- Sec. 4.19.3
9) Accessible lavatories shall be mounted with the rim 34 inches
maximum above the floor and a clearance of 29 inches minimum
from the floor to the bottom of the front edge of the apron.
-- Sec. 4.20.2.1 & Fig. B4.20.3.1
10) It shall extend 17 inches minimum from the wall. The clear knee
space shall be 8 inches in depth minimum at 27 inches minimum
above the floor and 11 inches in depth minimum at 9 in minimum
above the floor. The dip of the overflow shall be ignored when
checking the clearances. -- Sec. 4.20.3.1 & Fig. B4.20.3.1
11) A clear floor space of 30 X 48 inches minimum shall be provided
in front of the lavatory and shall extend 19 inches maximum
under the lavatory. -- Sec. 4.20.3.2 & Fig. B4.20.3.2
12) Water supply and drain pipes under lavatories shall be
insulated or otherwise treated to protect against contact.
-- Sec. 4.20.4
13) The bottom of mirror is required to be within 38 inches of
the floor. -- Sec. 4.16.6 & Fig. B4.20.3.1
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
Page # 12
GLAZING REQUIREMENTS
All glazing in hazardous locations is required to be of safety
glazing material. -- Sec. 2406.3 & 2406.4
Locations:
1) Glazing in ingress and egress doors except jalousies.
2) Glazing in fixed and sliding panels of sliding door assemblies
and panels in swinging doors other than wardrobe doors.
3) Glazing in storm doors.
4) Glazing in all unframed swinging doors.
5) Glazing in doors and enclosures for hot tubs, whirlpools, saunas,
steam rooms, bathtubs and showers. Glazing in any portion of a
building wall enclosing these compartments where the bottom exposed
edge of the glazing is less than 60 inches above a standing surface
and drain inlet.
6) Glazing in fixed or operable panels adjacent to a door where the
nearest exposed edge of the glazing is within a 24 -inch arc of
either vertical edge of the door in a closed position and where the
bottom exposed edge of the glazing is less than 60 inches above the
walking surface.
7) Glazing in an individual fixed or operable panel, other than those
locations described in items 5 and 6 above, than meets all of the
following conditions:
A. Exposed area of an individual pane greater than 9 square feet.
B. Exposed bottom edge less than 18 inches above the floor.
C. Exposed top edge greater than 36 inches above the floor.
D. One or more walking surfaces within 36 inches horizontally of
the plane of the glazing.
8) Glazing in railings regardless of height above a walking surface.
Included are structural baluster panels and nonstructural in -fill
panels.
9) Glazing in walls and fences used as the barrier for indoor and
outdoor swimming pools and spas when the bottom edges is less than
60 inches above the pool side and the glazing is within 5 feet
of the pool or spa water's edge.
10) Glazing in walls enclosing stairway landings or within 5 feet of
then bottom and top of stairways where the bottom edge is less
than 60 inches above the walking surface.
Code review for:
Project Id.: Dr. Christensen
Address: 370 East 1st South
Page # 13
CRAWLSPACE REQUIREMENTS:
1) Provide ventilation either by mechanical means or by openings in
exterior walls. Opening shall provide a net area of not less than
1 square foot for each 150 square feet of area in crawl space.
Openings shall be distributed on two opposite sides and be located
as close to corners as practical. -- Sec. 2306.7
Note: Vent openings may be reduced to 10o of the above if ground
surface area is covered with an approved vapor barrier and the
building official approves.
2) Provide 18 -inch by 24 -inch access opening to the crawl space area.
Note: Opening may be required to be larger if mechanical equipment
is located in the crawl space. -- Sec. 2306.3
3) Unless the wood is listed as an approved wood of natural resistance
to decay or treated wood, the minimum clearance between exposed earth
and floor joist is 18 inches. The minimum clearance to beams and
girders is 12 inches. -- Sec. 2306.3
ATTIC REQUIREMENTS:
1) Provide an access to all attic areas with a clear height of 30 inches
or more. The minimum size is 22 inches by 30 inches. There must be 30
inches or more clear height above the access. -- Sec. 1505.1
2) Provide ventilation in all attic areas. The net free vent area is
to be not less than 1 square foot for each 150 square feet of attic
area. The vent area may be 1/300 if at least 50% of the required
ventilating area is provided by ventilators located in the upper
portion of the attic. The upper ventilators must be at least 3 feet
above the eave or cornice vents. -- Sec. 1505.3, Exception 1
The vent area may be 1/300 provided a vapor retarder having a
transmission rate not exceeding 1 perm is installed on the warm side
of the attic insulation. -- Sec. 1505.3, Exception 2
3) Where eave or cornice vents are installed, insulation shall not block
the fee flow of air. A minimum of 1 inch of air space shall be
provided between the insulation and roof sheathing. -- Sec. 1505.3