HomeMy WebLinkAboutFIRE SYSTEM PLAN - 08-00277 - Albertsons - Fire Alarm4 �1 t t t t SPRINKLER SCHEDULE & LEGEND EXISTING _ NEW NEW FIRE PROTECTION PLAN EXISTING J J" APPROXIMATELY 9,500 SQ FT 1/8" = 1' — 0" NEW EXISTING NEW EXISTING NEW ISYMBOLI SIN PHOENIX SCOPE OF WORK CLOUDED AREAS I K —FAC -- REMOVE I TEMP. DROP, PIPE AND' 1. ADD NEW PENDENTS TO ACCOMODATE NEW CEILING TILE SPRINKLER TO •E LINE CSC MODEL BV -QR SSP PRODUCE 2. ADD NEW UPRIGHTS (2) WHERE INDICATED 1 200 3. REPLACE ALL HEADS IN MEAT CUT & WRAP ROOM WITH NEW N/A SPRINKLER SCHEDULE & LEGEND EXISTING _ NEW NEW FIRE PROTECTION PLAN EXISTING J J" APPROXIMATELY 9,500 SQ FT 1/8" = 1' — 0" NEW EXISTING NEW EXISTING NEW ISYMBOLI SIN PHOENIX SCOPE OF WORK RESP. I K —FAC ALBER TSON'S T1. I TEMP. I FNISH 1. ADD NEW PENDENTS TO ACCOMODATE NEW CEILING TILE QTY. •E LAYOUT USING NEW TYCO MODEL TY -FRB - RECESSED HEADS CSC MODEL BV -QR SSP OR 2. ADD NEW UPRIGHTS (2) WHERE INDICATED 1/2" 200 3. REPLACE ALL HEADS IN MEAT CUT & WRAP ROOM WITH NEW N/A CORRISION RESISTANT HEADS AND ESCUTCHEONS, TY3231 TYCO MODEL TY -FRB SSP 4. DEMO CIRCLED HEADS AND PIPE 5.6 172 2 5. REPLACE SIDEWALL HEAD (1) IN ENTRANCE CANOPY WITH WHITE RECESSED NEW HEAD. TY3231 6. INSTALL RECESSED SPRINKLERS IN ALL NEW SOFFIT AREAS OR 5.6 OR WHERE CEILINGS ARE AT 10 FEET OR LOWER, 155 WHITE 7. REPLACE ALL 2ND PIECE CANOPY'S IN ENTIRE STORE. 2 >E 8. GO THROUGH STORE AND REMOVE LINT ON ALL HEADS. CSC MODEL HSW OR 9. ADD NECESSARY ARM OVERS WHERE NEEDED 1/2" 3EE N 10. FIELD VERIFY ADDED BRANCH LINES SIZES ARE CONSISTENT CANOPY ARE WITH ESTABLISHED DESIGN MODEL. TY3331 TYCO MODEL TY -FRB HSW 11. FIELD VERIFY HEAD PLACEMENT DOESN'T CONFLICT WITH 5.6 1/2" OTHER TRADES. 11 1 12, THE EXISTING RISER SHALL NOT BE MOVED. HOWEVER, HE VALVES, ALARM DEVICES, GAGES, ETC., SHALL BE CHECKED FOR OR 5.6 PROPER OPERATION, AND, IF FOUND TO BE DEFECTIVE, REPAIRED 155 CHROME OR REPLACED AS NECESSARY, REPLENISH SPARE HEAD H CABINET TO PROVIDE A MINIMUM OF 12 SPARE SPRINKLERS, TYCO MODEL DRY DS -1 SSP OR 13, PER NFPA 13 2421.6 NO HYDROSTATIC TEST IS REQUIRED. 112" 155 SPRINKLER SCHEDULE & LEGEND EXISTING _ NEW NEW FIRE PROTECTION PLAN EXISTING J J" APPROXIMATELY 9,500 SQ FT 1/8" = 1' — 0" NEW EXISTING NEW EXISTING NEW ISYMBOLI SIN I SPRINKLER DESCRIPTION RESP. I K —FAC ORIFICE I TEMP. I FNISH ESCUTCHEON QTY. •E CSC MODEL BV -QR SSP OR 5.6 1/2" 200 WHITE N/A • TY3231 TYCO MODEL TY -FRB SSP OR 5.6 172 2 155 WHITE RECESSED 58 TY3231 TYCO MODEL TY -FRB SSP OR 5.6 1/2" 155 WHITE 1" DROP 2 >E CSC MODEL HSW OR 5.6 1/2" 3EE N TE FOR FRONT CANOPY ARE TY3331 TYCO MODEL TY -FRB HSW OR 5.6 1/2" 11 1 1 HE CSC MODEL DRY SSP OR 5.6 1/2" 155 CHROME N/A H TY3235 TYCO MODEL DRY DS -1 SSP OR 5.6 112" 155 CHROME N A 4 OE I CSC MODEL BV -QR SSU OR 5.6 1/2 200 BRASS N A HEAD CABINET WITH MIN. 6 SPARE HEADS & WRENCH ES PROVIDED TOTAL COUNT THIS JOB = 67 1 I r_ l CENTRAL MODEL DS -1 5.6K— factor 1' Orf CHROME DRY PENDENT �rtetaining strap " / l09 -o BEAM CLAMP , F. FHANNGER LIM lie PHARMA Rem taming Strap ALL THREAD ROD CY C37 f 1 0 00 9' 8" HANGER RING TS H T 5 , BEAM CLAMP ' _ '0 E E _ 108'—C)" EXIST. HT. 109' -8" p E 1 EXIST. O O ■ 109' -11.. / EXIST. HT. O 112' -2" O STEEL DECKING minimum M 15 go " steal deck TEX 50 — _ METAL SAMMY SCREW A.T. ROD NOTE: TO BE USED ONLY WITH 1" PIPE! EXIST. HT. , 109' -11" REPLACE EXISTING DRY SIDE WALL FIRE SPRINKLER IN FRONT CANOPY THAT IS MISSING HANGER MNG DEFLECTOR WITH NEW SPRINKLER. NEW , SPRINKLER MALL BE SAME TYPE, FINISH AND TEMPERATURE RATING AS EXISTING. SM DECK SAMMY SCREW HANGER ASSMLY xTS i - . -- - . —� - - REAR PIPING LEG , LEFT RIGHT EXISTING PIPING O ( C Z NEW PIPING FRONT PHOENIX FIRE I C TION PR 0 1388 N. 39TH STREET NAMPA, IDAHO (208) 468 -9115 (208) 461-9117 fax ID. LIC. F. P. S. C. #108 NPUBLIC YORKS LIC. #16630-C-4(13930) FILE NAME: 803 TI FP.DWG DRAWN BY: Jeff Chelgren CHECKED BY: Trent J Bice CET III # 107524 ALBERTSON'S REXBURG T.I. 190 N. 2ND EAST REXBURG, IDAHO FIRE PROTECTION PLAN DATE FEB. 2008 SCALE: AS NOTED BLD: TDB #- 803 NOTICE IT IS THE OWNER'S RESPONSIBILITY TO PROVIDE HEAT ADEQUATE TO PREVENT FREEZING THROUGH- OUT THE WET PIPE SPRINKLER SYSTEM AREAS AND ALSO IN ENCLOSURES FOR DRY PIP, DELUGE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO THE SPRINKLER SYSTEMS, CONTRACT WITH BATEMAN —HALL, INC. ADDRESS: 1405 Foote Drive ADDRESS: Idaho Falls, Idaho 83403 -1464 PHONE NUMBER: 208- 523 -2681 FAX: 208- 524 -4435 NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES The reeds of this mpntubm show that Trent J Bice Automatic Sprinkler System Ayout 00301 / LEVEL m is certified in the technical un(a) Technldan GartlBcation No. 107524 txrtiseation(a) Valid 78/01/2009 APPROVAL STAMP PANS ACCEPTED >! B IC" ; i T( COMMiEWS fi4N CHANGES ICS DIC ATELS xRy l i P�F r`c '_", FP .!453TALL f`. nEVIEW r BY DATE ■ -i ■�i