FIRE SPRINKLER PLANS - 05-00053 - The Village Apartments - Bldg 8 21 Units
0 11 12 13 14 15 16 0 i8 ig 20 21 A B TYCO SERIES TY —FRB UPRIGHT 2) SYSTEM DESIGN TO START AT NODE U1 AND CONTINUE THROUGHOUT EACH BUILDING. SYSTEMS DESIGNED PER NFPA 13R FOR RESIDENTIAL OCCUPANCY. C D E I G H J 12 L M 7 P Ifl I:. S EQUIPMENT & DEVICE LEGEND DEVICE MANUFACTURER /MODEL 1 -1/2" DOUBLE CHECK ASSEMBLY AMES SERIES 2000B 1 -1/2" BUTTERFLY VALVES W /TAMPER BUTTERBALL BB -SCS02 1 -1/2" CHECK VALVE UNITED BRASS WORKS MODEL 99S SWING CHECK VALVE RESIDENTIAL SIDEWALL SPRINKLER APARTMENTS TYCO SERIES LFII RESIDENTIAL SIDEWALL, K =4.2, 155, MAXIMUM SPACING 16'- 0x16' -0 (256 sq.ft.) NO MORE THAN 8' -0 OFF ANY SIDE WALL RESIDENTIAL PENDENT SPRINKLER APARTMENTS TYCO SERIES LFII RESIDENTIAL PENDENT, K =4.9, 155', MAXIMUM SPACING 18'- 0x18' --0 (324 sq.ft.) NO MORE THAN 9' -0 OFF ANY WALL UPRIGHT SPRINKLER RISER ROOM TYCO SERIES TY -FRB, UPRIGHT, K =5.6, 155' TYCO SERIES LFII RESIDENTIAL RECESSED SIDEWALL 7lt8s1tH' (99,9x3,2 mm} MOUNTING I Face OF SURFACE –� SPRINIQ.ER FITTING TOP -OF -. CLOSUREI�ii�_ DEFLECTOR �� f 1 ; TY7334 ( [ 2 -7f6` DIA. I C73,0 1 — — 2-114' CIA- t ( mm) 7195` (11,1 mm) MOUNTING � ®r PLATE END-CF I DEFLECTOR BOSS 1 -W (34,0 mm) [ 112• (92,7 rim) 1.1/9" (20.6 mm) 114" (6,4 mm) UPRIGHT ON 1" RISER — — — — — INSTALLATION /LAYOUT DRAWINGS INDICATE THE PROPOSED STANDARD UPRIGHT HEAD — — — — — — —L}— STANDARD PENDENT HEAD — — — — — — PENDENT HEAD BELOW CEILING — — — — — (•}— STANDARD UPRIGHT SIDEWALL LOCATION OF PIPING, PIPE STANDS, COMPONENTS, ETC. STANDARD PENDENT SIDEWALL HORIZONTAL SIDEWALL — — — — — — — --� HEAD ABOVE & BELOW CEILING — — — — DRY PENDENT HEAD — — — — — FIELD ADJUSTMENTS OF PIPE ROUTING, PIPE LENGTHS, AND FLUSH TYPE HEAD — — — — — — — —— EARTHQUAKE BRACE RISE UP ----- - - - - -- — o-- DROP DOWN---- - - - - POSITIONING OF HANGERS, ETC. SHALL BE ANTICIPATED AND I tvlUUNTING - T EXPECTED. THESE CHANGES SHALL MEET NFPA REQUIREMENTS (3,2 ntm) j CLOSURE TY2234 1.318' (34,9 mm) AND ARE TO BE RED -LINED AND INCORPORATED ONTO THE "AS BUILT" DRAWINGS ACCORDINGLY. NOTICE NOMENCLATURE IT IS THE OWNER'S RESPONSIBILITY TO PROVIDE ADEQUATE CROSS MAIN DESIGNATION - - - - I CRQSSMAIN 'A• ALARM VALVE & RISER - - - - - ®-- CONTROL VALVE - - - - - - - -p}- HEAT TO PREVENT FREEZING THROUGHOUT WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE AND OTHER TYPES OF VALVES CONTROLLING WATER FEE D MAIN DESIGNATION1 HORIZONTAL ALARM VALVE - - - - - - KEY VALVE - - - - - - - - - --3ik-- SUPPLIES TO SPRINKLER SYSTEMS. ELEVATION TO CL OF PIPE AS ( NOTED - - ) F - 1 DRY PIPE VALVE &RISER - - - - ®- POST INDICATOR VALVE (PIV) - - - WATER SUPPLY INFORMATION LINE DESIGNATION - - - - - - - - - O DELUGE VALVE & RISER - - - - PIV W /TAMPER SWITCH - - - - - -p�- STAnc 90 p si RESIDUAL 85 psi CALCULATION DESIGNATION - - - - - - Q CHECK VALVE - - - - - - - - FIRE DEPARTMENT CONNECTION - - - V GPM LOWING 1252 FLOW DATE 09/05/03 F Pioneer Road NEW UNDERGROUND - - - - - - - - �� FLOW SWITCH - - - - - - - - W FLUSH FIRE DEPT CONNECTION L N SOURCE OF INFORMATION 3 -D Fire Protection Inc. EXISTING UNDERGROUND - - - - - - WATER MOTOR GONG - - - - - ® FIRE HYDRANT - - - - - - - - Waterf low Test REVISIONS - - - - - - - - - - - - - ELECTRIC BELL - - - - - -- ® FIRE HYDRANT W /PUMP - - -- c-+� -� TYCO SERIES LFII RESIDENTIAL RECESSED SIDEWALL 7lt8s1tH' (99,9x3,2 mm} MOUNTING I Face OF SURFACE –� SPRINIQ.ER FITTING TOP -OF -. CLOSUREI�ii�_ DEFLECTOR �� f 1 ; TY7334 ( [ 2 -7f6` DIA. I C73,0 1 — — 2-114' CIA- t ( mm) 7195` (11,1 mm) MOUNTING � ®r PLATE END-CF I DEFLECTOR BOSS 1 -W (34,0 mm) [ 112• (92,7 rim) 1.1/9" (20.6 mm) 114" (6,4 mm) UPRIGHT ON 1" RISER — — — — — — — —p— STANDARD UPRIGHT HEAD — — — — — — —L}— STANDARD PENDENT HEAD — — — — — — PENDENT HEAD BELOW CEILING — — — — — (•}— STANDARD UPRIGHT SIDEWALL FACE OF I STANDARD PENDENT SIDEWALL HORIZONTAL SIDEWALL — — — — — — — --� HEAD ABOVE & BELOW CEILING — — — — DRY PENDENT HEAD — — — — — — — —— FLUSH TYPE HEAD — — — — — — — —— EARTHQUAKE BRACE RISE UP ----- - - - - -- — o-- DROP DOWN---- - - - - -- —o-- GENERAL NOTES TYPICAL WET PIPE RISER DETAIL NOT TO SCALE TYCO SERIES LFII RESIDENTIAL RECESSED PENDENT I ° - -- 2 -718" DIA.. 1. All— thread rod A. Top Beam Clamp 7116_1/8' { (73,0 mm) 1/2' (12,7 mm) (11,1x3,2 mm) f 2-114° DIA. 14' (— 6,4 mm) I FACE OF I (57,2 mm) SPRINKLER I MOUNTING FITTINGS I 8. H. Wing Toggle PLATE 9. Special (See Detail) I. Side Beam Bracket J. Speedy Fastener � I tvlUUNTING 1/8" SURFACE (3,2 ntm) j CLOSURE TY2234 1.318' (34,9 mm) 1 -118" (28,6 mm) HANGERS 1. All— thread rod A. Top Beam Clamp Sprinkler 2_U —hook B. Nut & Washer 3. Coach screw C. Unistrut Nut 4. Eye —rod D. Drop —in Anchor 5. lI —bolt E. Hilti Stud 6. Pipe strap F. Lag Bolt 7. Bracket G. Rod Coupling 8. H. Wing Toggle 9. Special (See Detail) I. Side Beam Bracket J. Speedy Fastener ssu* DEFLECTOR 7/16" i (11,1 mm) NOMINAL h4AKE -IN 2 3116" N (55 n)m) I U2" NPT *x RISER LEGEND NOTE: ALL ELECTRICAL ALARM WIRING OR WIRING OF ANY KIND TO BE BY OTHERS. O1 6" DUCTILE IRON UNDERGROUND. TO BE FLUSHED AND TESTED PRIOR TO CONNECTION. O2 REQUIRED CLEAR SPACE AROUND RISER Q3 2" GALVANIZED TEE FOR DOMESTIC WATER (BY OTHERS) ® 2" TEE FOR FLUSHING O5 SUPPLY SIDE PRESSURE GAUGE © 1 -1/2" DOUBLE CHECK BACKFLOW PREVENTER W /BUTTERFLY VALVES (WITH TAMPER SWITCHES) iJ7 1 -1/2" CHECK VALVE ® 2%2-1/2" INCREASER O9 BALL DRIP VALVE 10 2 -1/2" SINGLE FIRE DEPARTMENT CONNECTION 11 1 -1/2" RISER MANIFOLD 12 HYDRAULIC CALCULATIONS RISER PLACARD 13 WATERFLOW SWITCH 14 SYSTEM SIDE PRESSURE GAUGE 15 1" BALL VALVE AND INSPECTOR'S TEST 16 1 -1/4" MAIN DRAIN BALL VALVE 17 1-1/4" MAIN DRAIN TO BLDG EXTERIOR 18 SPLASH BLOCK 19 ELECTRIC BELL (BY OTHERS) 20 SPARE HEAD BOX WITH SPARE SPRINKLER HEADS AND WRENCH 21 SEISMIC ''BRACE - F DAL AN" t "'r '�d S AN a , S vStfiL A.. CH AN" f . f ice" � � { � L% �d .D COUNT 3 -D FIRE PROTECTION, INC. Design • Installation Maintenance • Inspection For Service or Repair & 24 Hrs. Emergency Service Please Call (208) 525 -8377 Fax (208) 525–$381 P.O. Box 50845 Idaho Falls, Idaho 83405 -0845 v o- C 3: W 2nd S -N- o V' W 4th S �—~'� W 7th S AREA OF WORK PIONEER ROAD REXBURG VICINITY MAP To Idaho Falls NO SCALE CAROL HENSCHEID NICET III NO. 100827 ENGINEERING TECH. 2005 I 0 10' 60' 120' �` SCALE: 1 " = 60' -0 Contract Name: Scale: As Noted The Village Apartments Drawn: C. Henscheid Rexburg, Idaho Checked: L. Hayward Phase 2 Date: 05/25/05 Contract with: Revision: Rocky Mountain Construction 560 West 1 st North Rigby, Idaho 83442 Description: Site Plan /Riser Detail Contract # 1154 -205 Drawing F -1 of 13 1) 3 -D FIRE PROTECTION TO BEGIN WORK AT TIE -IN TO UNDERGROUND IN HEATED RISER ROOMS AS SHOWN ON DRAWINGS. 3) THE SYSTEMS THROUGHOUT EACH BUILDING ARE WET -PIPE SYSTEMS AND MUST HAVE ADEQUATE PROTECTION TO PREVENT FREEZING. 4) ALL EQUIPMENT AND MATERIAL TO BE U/L LISTED OR FM APPROVED. DOMESTIC MADE NOT REQUIRED. ALL SCHEDULE 40 STEEL PIPE TO BE THREADED AND /OR ROLLED GROOVED. ALL THIN WALL PIPE ( "DYNA- FLOW ") TO BE ROLLED GROOVED USING GROOVED TYPE COUPLINGS AND FITTINGS APPROVED FOR FIRE PROTECTION SYSTEM USE. ALL CPVC PLASTIC PIPE TO BE UL /FM APPROVED. ALL CPVC FITTINGS, SOLVENTS, & CEMENT TO BE APPROVED FOR TYPE OF CPVC PLASTIC PIPE USED. ALL PIPE TO EXTERIOR OF BUILDING TO SCHEDULE 40 GALVANIZED. TYPE OF PIPING FEED MAIN PIPING: CPVC PLASTIC CROSS MAIN PIPING: CPVC PLASTIC BRANCH LINE PIPING: CPVC PLASTIC 5) EACH SYSTEM TO BE INSTALLED, FLUSHED AND TESTED IN ACCORDANCE WITH NFPA 13. 6) ALARM DEVICE FOR EACH SYSTEM IS AN AMES 20008 DOUBLE CHECK VALVE BACKFLOW PREVENTER WITH TAMPER SWITCHES. FLOW INDICATOR AND VALVE TAMPER TO BE CONNECTED TO FIRE ALARM SYSTEM IF APPLICABLE. 7) ALL ELECTRICAL, ALARM, & WIRING, OF ANY KIND, IS BY OTHERS. 8) ALL PIPING TO BE HUNG FROM STRUCTURAL MEMBERS BY USE OF PIPE STRAPS AS SHOWN IN HANGER DETAILS. 9) EARTHQUAKE BRACING TO BE SIZED AND INSTALLED ACCORDING TO THE LATEST NFPA 13 EDITION FOR SEISMIC ZONE 3. 10) TYPE OF CONSTRUCTION: NEW WOOD TRUSS BUILDING FITTERS NOTES 1) ALL CPVC PLASTIC PIPE DIMENSIONS SHOWN ARE CENTER TO CENTER OR CENTER TO END. DIMENSIONS SHOWN FOR THREADED PIPE IS CUT LENGTH. 2) WHERE FIRE SPRINKLER PIPING: PENETRATES IDENTIFIED FIRE WALLS, FIRE CAULK AND SEAL PENETRATIONS AS REQUIRED. 3) COORDINATE THE LOCATION OF ALL SPRINKLER PIPING WITH OTHER SUBCONTRACTORS ON THE JOB TO AVOID POSSIBLE OBSTRUCTIONS TO SPRINKLER DISCHARGE. 4) LOCAL AUTHORITY HAVING JURISDICTION: REXBURG FIRE CHIEF CHRIS HUSKINSON- TELEPHONE: 359 -3010 To St Anthony TEST HYDRANT FLOW TEST CONDUCTED BY 3 -D FIRE PROTECTION INC. STATIC: 90 psi SITE PLAN RESIDUAL: 85 psi FLOWING: 1252 gpm SCALE: 1" = 60' -0 A B c D E F PIPE STRAP G TENT INSULATION OVER PLASTIC ASQUEEN /PIPING AND SECURE TO TRUSS CHORD OF WOOD TRUSS H PIPE STRAP 3/8" (00) ll(/ O\ \\ \111 SCREW TYP 2x4 STUD WALL 3/8" PIPE TENTING DETAIL NOT TO SCALE J K L M N - FIRST LEVEL FIRE P j TENT PIPING WITH PLASTIC VISQUEEN (OR EQUAL) AND SECURE TO TRUSS FITTERS NOTES 0 P 1) ALL CPVC PLASTIC PIPE DIMENSIONS SHOWN ARE CENTER TO CENTER OR CENTER TO END. DIMENSIONS SHOWN FOR THREADED PIPE IS CUT LENGTH. 2) WHERE FIRE SPRINKLER PIPING PENETRATES IDENTIFIED FIRE WALLS, FIRE CAULK AND SEAL PENETRATIONS AS REQUIRED. 3) COORDINATE THE LOCATION OF ALL SPRINKLER PIPING WITH OTHER SUBCONTRACTORS ON THE JOB TO AVOID POSSIBLE OBSTRUCTIONS TO SPRINKLER DISCHARGE. N PLAN VIEW PIPE STRAP HANGER DETAIL NOT TO SCALE 4) LOCAL AUTHORITY HAVING JURISDICTION: REXBURG FIRE CHIEF CHRIS HUSKINSON- TELEPHONE: 359 -3010 APPROVAL STAMP R S T SECOND LEVEL FIRE • PLAN NOTICE I NOMENCLATURE INSTALLATION/LAYOUT OMENCLATURE INSTALLATION /LAYOUT DRAWINGS INDICATE THE PROPOSED LOCATION OF PIPING, PIPE STANDS, COMPONENTS, ETC. FIELD ADJUSTMENTS OF PIPE ROUTING, PIPE LENGTHS, AND POSITIONING OF HANGERS, ETC. SHALL BE ANTICIPATED AND EXPECTED. THESE CHANGES SHALL MEET NFPA REQUIREMENTS AND ARE TO BE RED -LINED AND INCORPORATED ONTO THE "AS- BUILT" DRAWINGS ACCORDINGLY. IT IS THE OWNER'S RESPONSIBILITY TO PROVIDE ADEQUATE HEAT TO PREVENT FREEZING THROUGHOUT WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS. WATER SUPPLY INFORMATION STATIC 90 psi RESIDUAL 85 psi GPM FLOWING 1252 FLOW DATE 09/05/03 LOCATION Pioneer Road SOURCE OF INFORMATION 3 -D Fire Protection Inc. Waterflow Test CROSS MAIN DESIGNATION - - - - CROSSMAIN "A ALARM VALVE & RISER - - - - - ® - FEED MAIN DESIGNATION - - - - - - - FM A' HORIZONTAL ALARM VALVE - - - - --�- ELEVATION TO CL OF PIPE (AS NOTED) - - ] DRY PIPE VALVE & RISER - - - - �- LINE DESIGNATION - - - - - - - - - 0 DELUGE VALVE & RISER - CALCULATION DESIGNATION - - - - - - 0 CHECK VALVE - - - - - - - - - NEW UNDERGROUND - - - - - - - - =mcmom = FLOW SWITCH - - - - - - - - EXISTING UNDERGROUND - - - - - - WATER MOTOR GONG - - - - - REVISIONS - - - - - - - - - - - - - 0 ELECTRIC BEL - - - - - -- RE.V}EWEE By ___._._ CONTROL VALVE - - - - - - - - {- KEY VALVE --- - - - - -- -4E- POST INDICATOR VALVE (PIV) - - -q- — — PIV W /TAMPER SWITCH - - - - - - {�- FIRE DEPARTMENT CONNECTION - - -V FLUSH FIRE DEPT CONNECTION - - ^ FIRE HYDRANT - - - - - - - - c--o- -) FIRE HYDRANT W /PUMP - - - - c UPRIGHT ON 1" RISER — — — — — — — —@— STANDARD UPRIGHT HEAD — — — — — — —0-- STANDARD PENDENT HEAD — — — — — — PENDENT HEAD BELOW CEILING — — — — �-- STANDARD UPRIGHT SIDEWALL — — — — —� STANDARD PENDENT SIDEWALL 7. Bracket HORIZONTAL SIDEWALL — — — — — — — —� HEAD ABOVE & BELOW CEILING — — — — DRY PENDENT HEAD — — — — — — — FLUSH TYPE HEAD — — — — — — — —— EARTHQUAKE BRACE SU BJC... �k RISE UP ----- - - - - -- —@— DROP DOWN---- - - - - -- —a HANGERS 1. All— thread rod A. Top Beam Clamp 2. U —hook B. Nut & Washer 3. Coach screw C. Unistrut Nut 4. Eye —rod D. Drop —in Anchor 5. U —bolt E. Hilti Stud 6. Pipe strop F. Lag Bolt 7. Bracket G. Rod Coupling 8. H. Wing Toggle 9. Special (See Detail) I. Side Beam Bracket J. Speedy Fastener �, IT Z, 5 ... Fin. O ,.. .iii` " Can T Temp. S Symb. Q Qty. 3 3 FIRE PROTECTION, INC. 8F )AHO PLANS � f:r4'� c� SU BJC... �k � Ir(N MENTS AND CHANGES INF,`!(`ATETD 3N sir "� INSTACLA^ TION IS Sc1° !� i !, CS a RE.V}EWEE By ___._._ �, IT Z, Sprinkler T Type F Fin. O HEAD C COUNT Can T Temp. S Symb. Q Qty. 3 3 FIRE PROTECTION, INC. Contract Name: The Village Apartments Rexburg, Idaho Buildina 8 Contract with: Rocky Mountain Construction 560 West 1 st North Rigby, Idaho 83442 Description: Fire Protection Plan Scale: As Noted Drawn: C. Henscheid Checked: L. Hayward Date: 05/25/05 Revision: Contract # 1154 -205 Drawing: F -2 of 13 1 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Contract # 1154 -205 Drawing: F -2 of 13 1 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 A B C D E F G H J K L IN N SCALE: 1 SECTI BUILDING 1/8" = 1' -0 8' -0 9' -0 9' -0 FITTERS NOTES X 1) ALL CPVC PLASTIC PIPE DIMENSIONS SHOWN ARE CENTER TO CENTER OR CENTER TO END. DIMENSIONS SHOWN FOR THREADED PIPE IS CUT LENGTH. 2) WHERE FIRE SPRINKLER PIPING PENETRATES IDENTIFIED FIRE WALLS, FIRE CAULK AND SEAL PENETRATIONS AS REQUIRED. P 3) COORDINATE THE LOCATION OF ALL SPRINKLER PIPING WITH OTHER SUBCONTRACTORS ON THE JOB TO AVOID POSSIBLE OBSTRUCTIONS TO SPRINKLER DISCHARGE. R BUILD SECTIO SCALE: 1/8" = 1' -0 S F -2, F -3 CONTROL VALVE - - - - - - - INSTALLATION /LAYOUT DRAWINGS INDICATE THE PROPOSED KEY VALVE ---- - - - - -� - - -a- POST INDICATOR VALVE (PIV) - - - - PIV W /TAMPER SWITCH - - - - - LOCATION OF PIPING, PIPE STANDS, COMPONENTS, ETC. FIRE DEPARTMENT CONNECTION - - 5. U -bolt FLUSH FIRE DEPT CONNECTION - - - - - •4 FIRE HYDRANT - - - - - - - - FIELD ADJUSTMENTS OF PIPE ROUTING, PIPE LENGTHS, AND FIRE HYDRANT W /PUMP - - - - c-ba DRY PENDENT HEAD - - - - - - - - FLUSH TYPE HEAD - - - - - - POSITIONING OF HANGERS, ETC. SHALL BE ANTICIPATED AND EARTHQUAKE BRACE Drawing: RISE UP ----- - - - - -- -�- - T EXPECTED. THESE CHANGES SHALL MEET NFPA REQUIREMENTS AND ARE TO BE RED -LINED AND INCORPORATED ONTO THE "AS- BUILT" DRAWINGS ACCORDINGLY. NOTICE NOMENCLATURE IT IS THE OWNER'S RESPONSIBILITY TO PROVIDE ADEQUATE CROSS MAIN DESIGNATION - - - - I CROSS MAIN •A• ALARM VALVE & RISER - - - - - ®-- HEAT TO PREVENT FREEZING THROUGHOUT WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY FEED MAIN DESIGNATION- - - - - - - FM'A' HORIZONTAL ALARM VALVE - - - - -�- PIPE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES To SPRINKLER SYSTEMS. ELEVATION TO CL OF PIPE (AS NOTED) - - -[ DRY PIPE VALVE & RISER - - - - �- WATER SUPPLY INFORMATION LINE DESIGNATION - - - - - - - - - O DELUGE VALVE & RISER - - - - ®- STATI 90 psi RESIDUAL 85 i CALCULATION DESIGNATION - - - - - - Q CHECK VALVE - - - - - - - - GPM FLOWING 1252 FLOW DATE 09/ NEW UNDERGROUND - - - - - - - - FLOW SWITCH - - - - - - - - � LOCATION Pioneer Road SOURCE OF INFORMATION 3 -D Fire Protection Inc. EXISTING UNDERGROUND - - - - - - WATER MOTOR GONG - - - - - Waterflow Test REVISIONS - - - - - - - - - - - - - Q ELECTRIC BELL - - - - - F -2, F -3 CONTROL VALVE - - - - - - - -Q-- KEY VALVE ---- - - - - -� - - -a- POST INDICATOR VALVE (PIV) - - - - PIV W /TAMPER SWITCH - - - - - -p�{- FIRE DEPARTMENT CONNECTION - - 5. U -bolt FLUSH FIRE DEPT CONNECTION - - - - - •4 FIRE HYDRANT - - - - - - - - - - —� FIRE HYDRANT W /PUMP - - - - c-ba UPRIGHT ON 1" RISER - - - - - - - -O- STANDARD UPRIGHT HEAD - - - - - - -a- STANDARD PENDENT HEAD - - - - - - -�1-- PENDENT HEAD BELOW CEILING - - - - -O- STANDARD UPRIGHT SIDEWALL 5. U -bolt STANDARD PENDENT SIDEWALL - - - - - •4 HORIZONTAL SIDEWALL - - - - - - - —� HEAD ABOVE & BELOW CEILING - - - - DRY PENDENT HEAD - - - - - - - - FLUSH TYPE HEAD - - - - - - - -- EARTHQUAKE BRACE Drawing: RISE UP ----- - - - - -- -�- DROP DOWN---- - - - - -- -+- HANGERS 1. AIL- thread rod A. Top Beam Clamp 2. U -hook B. Nut & Washer 3. Coach screw C. Unistrut Nut 4. Eye -rod D. Drop -in Anchor 5. U -bolt E. Hilti Stud 6. Pipe s trap F. Lag Bolt 7. B r a c k et G. Rod Coupling 8. H. Wing Toggle 9. Special (See Detail) I. Side Beam Bracket Contract J. SDeedv Fastener 4) LOCAL AUTHORITY HAVING JURISDICTION: 4 N ) P:: REXBURG FIRE CHIEF CHRIS HUSKINSON- TELEPHONE: 359 -3010 APPROVAL STAMP CAROL HENSCHEID NICER III NO. 100827 �� m ENGIN [ � 2005 EERING TECH. �® E t�..., F i I P'� I"F 0 a¢_A1d I' r C) jF C7 i;� 4'�NrNTS AND G�fi��, d " TEi iNl , v „ I AL<L.ET, TER INSTALLA — — TION S SU4S ECT TO A", ( E�8I0 y 0 5' 10' 20' SCALE: 1/8" = 1' -0 HEAD COUNT Sprinkler Type I Fin. I Orif. I K -Fac. I Can I Temp. I Symb. I Qty Total 3 —D� FIRE PROTECTION, INC. besign • Installation Maintenance • Inspection 3 1 For Service or Repair D & 24 Hrs. Emer ency Service Please Call (208 525 -8377 Fax (208) 525— 381 3 -D P.O. Box 50845 Idahq Falls, Idaho 83405 -0845 1154- 205- 03.dwq Contract Name: The Village Apartments Rexburg, Idaho Building 8 Scale: As Noted Drawn: Henscheid __ - C_ Checked: L. Hayward Date: 05/25/05 Contract with: Rocky Mountain Construction 560 West 1 st North Idaho 83442 Revision: — Ri g by, Description: Fire Protection Plan Contract # 1154 -205 Drawing: F -3 of 13 THIRD LEVEL FIRE PROTECTION PLAN A PIPE STRAP zz SCREW (TYP)� B _ � co D F PIPE STRAP G TENT INSULATION OVER PLASTIC VISQUEEN /PIPING AND SECURE TO TRUSS CHORD OF WOOD TRUSS M 2x4 STUD WALL 3/8 WOOD TENT PIPING WITH PLASTIC VISQUEEN (OR EQUAL) AND SECURE TO TRUSS PIPE TENTING DETAIL NOT TO SCALE J K L a T1 FIRST LEVEL FIRE PROTECTION PLAN SCALE: 1/8" = 1' -0 FITTERS NOTES A 1) ALL CPVC PLASTIC PIPE DIMENSIONS SHOWN ARE CENTER TO CENTER OR CENTER TO END. DIMENSIONS SHOWN FOR THREADED PIPE IS CUT LENGTH. 2) WHERE FIRE SPRINKLER PIPING PENETRATES IDENTIFIED FIRE WALLS, FIRE CAULK AND SEAL PENETRATIONS AS REQUIRED. P 3) COORDINATE THE LOCATION OF ALL SPRINKLER PIPING WITH OTHER SUBCONTRACTORS ON THE JOB TO AVOID POSSIBLE OBSTRUCTIONS TO SPRINKLER DISCHARGE, N APPROVAL STAMP R S INSTALLATION /LAYOUT DRAWINGS INDICATE THE PROPOSED LOCATION OF PIPING, PIPE STANDS, COMPONENTS, ETC. FIELD ADJUSTMENTS OF PIPE ROUTING, PIPE LENGTHS, AND POSITIONING OF HANGERS, ETC. SHALL BE ANTICIPATED AND - T EXPECTED. THESE CHANGES SHALL MEET NFPA REQUIREMENTS AND ARE TO BE RED -LINED AND INCORPORATED ONTO THE "AS- BUILT" DRAWINGS ACCORDINGLY. SECOIN' L EVEL PROTECTI NOTICE --- NOMENCLATUR �- IT IS THE OWNER'S RESPONSIBILITY TO PROVIDE ADEQUATE CROSS MAIN DESIGNATION - - - - I C R O SSMAIN "el ALARM VALVE & RISER - - - - - �- HEAT TO PREVENT FREEZING THROUGHOUT WET PIPE FLUSH FIRE DEPT CONNECTION - - " FIRE HYDRANT -- - - - - -- c-o -) SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY FEED MAIN DESIGNATION- - - - - - - FM A HORIZONTAL ALARM VALVE - - - - -{- PIPE AND OTHER TYPES OF VALVES CONTROLLING WATER EARTHQUAKE BRACE White RISE UP ----- - - - - -- --o— SUPPLIES To SPRINKLER SYSTEMS. ELEVATION TO CL OF PIPE (AS LINE DESIGNATION - - - - CALCULATION DESIGNATION - NOTED) - - ] - - - - - 0 - - - - - 0 DRY PIPE VALVE & RISER - - - DELUGE VALVE & RISER - - - CHECK VALVE - - - - - - - - �-- - �- - -IV- WATER SUPPLY INFORMATION STAnC 90 psi RESIDUAL 85 Psi GPM FLOWING 1252 FLOW DATE 09/05/03 NEW UNDERGROUND - - - - - - - - FLOW SWITCH - - - - - - - - 0-7 LocnnoN Pioneer Road EXISTING UNDERGROUND - - - - - - WATER MOTOR GONG - - - - - SOURCE OF INFORMATION 3 -D Fire Protection Inc. Waterflow Test REVISIONS - - - - - - - - - - - - - Q ELECTRIC BEL - - - - - - - CONTROL VALVE - - - - - - - --- KEY VALVE --- - - - - -- �- POST INDICATOR VALVE (PIV) - - - -p�-- PIV W /TAMPER SWITCH - - - - - - FIRE DEPARTMENT CONNECTION - - y FLUSH FIRE DEPT CONNECTION - - " FIRE HYDRANT -- - - - - -- c-o -) FIRE HYDRANT W /PUMP - - - - c-&a UPRIGHT ON 1" RISER — — — — — — — —OO — STANDARD UPRIGHT HEAD — — — — — — —o— STANDARD PENDENT HEAD — — — — — — PENDENT HEAD BELOW CEILING — — — — --0— STANDARD UPRIGHT SIDEWALL 5. U —bolt STANDARD PENDENT SIDEWALL — — — — --•4 HORIZONTAL SIDEWALL — — — — — — — --� HEAD ABOVE & BELOW CEILING — — — — —� DRY PENDENT HEAD — — — — — — — FLUSH TYPE HEAD — — — — — — — —— EARTHQUAKE BRACE White RISE UP ----- - - - - -- --o— DROP DOWN — — — — — — — — — — —+-- HANGERS 1. All—thread rod A. Top Beam Clamp 2. U —hook B. Nut & Washer 3. Coach screw C. Unistrut Nut 4. Eye —rod D. Drop —in Anchor 5. U —bolt E. Hilti Stud 6. Pipe strap F. Lag Bolt 7. B racket G. Rod Coupling 8. H. Wing Toggle 9. Special (See Detail) I. Side Beam Bracket Tyco Series LFlI J. Speedy Fastener PLAN VIEW PIPE STRAP HANGER DETAIL NOT TO SCALE 4) LOCAL AUTHORITY HAVING JURISDICTION: REXBURG FIRE CHIEF CHRIS HUSKINSON- TELEPHONE: 359 -3010 CAROL HENSCHEID NICET III No. 100827 ENGINEERING TECH. 2005 0 5' 10' 20' SCALE: 1/8" = 1' -0 Contract Name: The Village Apartments Rexburg, Idaho Building 9 Contract with: Rocky Mountain Construction 560 West 1 st North Rigby, Idaho 83442 Description: Fire Protection Plan Scale: i A Drawn: HEAD COUNT L. Hayward e ti l .` ANtt Pal. %P. �t. ?�rF 1itiST ILLA- 4 ri {�d1� Type TION IS SuE 5Jt Off. REVIEWEOi Can CAROL HENSCHEID NICET III No. 100827 ENGINEERING TECH. 2005 0 5' 10' 20' SCALE: 1/8" = 1' -0 Contract Name: The Village Apartments Rexburg, Idaho Building 9 Contract with: Rocky Mountain Construction 560 West 1 st North Rigby, Idaho 83442 Description: Fire Protection Plan Scale: As Noted Drawn: HEAD COUNT L. Hayward Date: 05/25/0 Revision: 3 — D FIRE PROTECTION, INC. D esign • Installation Maintenance Inspection 3 �1 For Service or Repair D & 24 Hrs. E "r ency Service Please Call (208 525 -8377 Fox (208) 5225 - 381 3 -D P.O. Box 50845 Idaho Falls, Idaho 83405 -0845 Sprinkler Type Fin. Off. K —Fac. Can Temp. Symb. Qty. Tyco Series LFlI SW White - -- 4.2 White 155' Q 60 Tyco Series LFlI Pendent White - -- 4.9 White 155' OQ 106 Tyco Series TY —FRB Upright Brass 1/2" 5.6 - -- 155' 0 1 Total 93 1154- 205 -04.dw CAROL HENSCHEID NICET III No. 100827 ENGINEERING TECH. 2005 0 5' 10' 20' SCALE: 1/8" = 1' -0 Contract Name: The Village Apartments Rexburg, Idaho Building 9 Contract with: Rocky Mountain Construction 560 West 1 st North Rigby, Idaho 83442 Description: Fire Protection Plan Scale: As Noted Drawn: C. Henscheid Checked: L. Hayward Date: 05/25/0 Revision: Contract # 1154 -205 Drawing: F -4 of 13 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 2: 0 11 12 13 14 15 16 17 A B c D r F G H J K L1 L 26 27 28 29 30 31 BUILDING SECTION SCALE: 1/8" = 1'-0 F -4, F -5 A 8' -0 9' -0 9' -0 FITTERS NOTES 0 P 1) ALL CPVC PLASTIC PIPE DIMENSIONS SHOWN ARE CENTER TO CENTER OR CENTER TO END. DIMENSIONS SHOWN FOR THREADED PIPE IS CUT LENGTH. 2) WHERE FIRE SPRINKLER PIPING PENETRATES IDENTIFIED FIRE WALLS, FIRE CAULK AND SEAL PENETRATIONS AS REQUIRED. 3) COORDINATE THE LOCATION OF ALL SPRINKLER PIPING WITH OTHER SUBCONTRACTORS ON THE JOB TO AVOID POSSIBLE OBSTRUCTIONS TO SPRINKLER DISCHARGE. Loll APPROVAL STAMP R S B UIL D ING SECTI SCALE: 1/8" = 1' -0 F -4, F -5 CONTROL VALVE - - - - - - - INSTALLATION /LAYOUT DRAWINGS INDICATE THE PROPOSED KEY VALVE --- - - - - -- fir- POST INDICATOR VALVE (PIV) - - - -p�- PIV W /TAMPER SWITCH - - - - - LOCATION OF PIPING, PIPE STANDS, COMPONENTS, ETC. FIRE DEPARTMENT CONNECTION - - - V FLUSH FIRE DEPT CONNECTION - - — — — •4 FIRE HYDRANT - - - - - - - - FIELD ADJUSTMENTS OF PIPE ROUTING, PIPE LENGTHS, AND FIRE HYDRANT W /PUMP - - - - — — DRY PENDENT HEAD — — — — — — — FLUSH TYPE HEAD — — — — — — POSITIONING OF HANGERS, ETC. SHALL BE ANTICIPATED AND EARTHQUAKE BRACE RISE UP ----- - - - - -- —o— - T EXPECTED. THESE CHANGES SHALL MEET NFPA REQUIREMENTS CHANGES TION IS SUF;js d� 0 5' 10' 20' AND ARE TO BE RED -LINED AND INCORPORATED ONTO THE "AS- BUILT" DRAWINGS ACCORDINGLY. NOTICE NOMENCLATURE IT IS THE OWNER'S RESPONSIBILITY TO PROVIDE ADEQUATE CROSS MAIN DESIGNATION - - - - I CROSSMAIN n• ALARM VALVE & RISER - - - - - ®— HEAT TO PREVENT FREEZING THROUGHOUT WEr PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY FEED MAIN DESIGNATION- - - - - - - FM'A' HORIZONTAL ALARM VALVE - - - - -- PIPE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES To SPRINKLER SYSTEMS. ELEVATION TO CE OF PIPE (AS NOTED) - - -[ DRY PIPE VALVE & RISER - - - - ® - WATER SUPPLY INFORMATION LINE DESIGNATION - - - - - - - - - O DELUGE VALVE & RISER - - - - ®- STATIC 90 psi RESIDUAL 85 psi CALCULATION DESIGNATION - - - - - - 0 CHECK VALVE - - - - - - - - -tv- GPM FLOWING 1252 FLOW DATE 09/05/03 NEW UNDERGROUND - - - - - - - - - m FLOW SWITCH - - - - - - - - LOCATION Pioneer Road SOURCE OF INFORMATION 3 -D Fire Protection Inc. EXISTING UNDERGROUND - - - - - - WATER MOTOR GONG - - - - - Waterflow Test REVISIONS - - - - - - - - - - - - - Q ELECTRIC BELL - - - - - - - F -4, F -5 CONTROL VALVE - - - - - - - -- KEY VALVE --- - - - - -- fir- POST INDICATOR VALVE (PIV) - - - -p�- PIV W /TAMPER SWITCH - - - - - -D�- FIRE DEPARTMENT CONNECTION - - - V FLUSH FIRE DEPT CONNECTION - - — — — •4 FIRE HYDRANT - - - - - - - - — — —� FIRE HYDRANT W /PUMP - - - - — — UPRIGHT ON 1" RISER — — — — — — — —O— STANDARD UPRIGHT HEAD — — — — — — —a— STANDARD PENDENT HEAD — — — — — — — PENDENT HEAD BELOW CEILING — — — — —0-- STANDARD UPRIGHT SIDEWALL — — — — --a4 STANDARD PENDENT SIDEWALL — — — — — •4 HORIZONTAL SIDEWALL — — — — — — — —� HEAD ABOVE & BELOW CEILING — — — — DRY PENDENT HEAD — — — — — — — FLUSH TYPE HEAD — — — — — — — — — EARTHQUAKE BRACE RISE UP ----- - - - - -- —o— DROP DOWN---- - - - - -- —9 HANGERS 1. AIL— thread rod A. Top Beam Clamp 2. U —hook B. Nut & Washer 3. Coach screw C. Unistrut Nut 4. Eye —rod D. Drop —in Anchor 5. U —bolt E. Hilti Stud 6. Pipe strap F. Lag Bolt 7. Bracket G. Rod Coupling 8. H. Wing Toggle 9. Special (See Detail) I. Side Beam Bracket J. Speedy Fastener 4) LOCAL AUTHORITY HAVING JURISDICTION: REXBURG FIRE CHIEF CHRIS HUSKINSON- TELEPHONE: 359 -3010 HEAD COUNT rr�� Sprinkler Type Fin. Orif. K —Fac. Can Temp. Symb. Qty. 3 FIRE PROTECTION, I N C. Design • Installation Maintenance • Inspection For Service or Repair D & 24 Hrs. Emer ency Service Please Call 208 525 -8377 Fax (208) 55— 381 3 —D P.O. Box 50845 Idaho Falls, Idaho 83405 -0845 Total 1154- 205 -05.dw Contract Name: The Village Apartments Rexburg, Idaho Buildina 9 Contract with: Rocky Mountain Construction 560 West 1 st North Rigby, Idaho 83442 Description: Fire Protection Plan Scale: As Noted Drawn: C. Henscheid Checked: L. Hayward Date: 05/25/05 Revision: Contract # 1154 -205 Drawing: F -5 of 13 THIRD LEVEL FIRE PROTECTION PLAN SCALE: 1/8" = 1' -0 CAROL HENSCHEID NICET III NO. 100827 ENGINEERING TECH. Vol V: 0 " r[ PLANS +''- �� ,�t n c r (_ r0EN S AND �,�, � ��, C..r � 1 Arta. INSTALLA.. � - CHANGES TION IS SUF;js d� 0 5' 10' 20' SCALE: 1/8" = 1' -0 HEAD COUNT rr�� Sprinkler Type Fin. Orif. K —Fac. Can Temp. Symb. Qty. 3 FIRE PROTECTION, I N C. Design • Installation Maintenance • Inspection For Service or Repair D & 24 Hrs. Emer ency Service Please Call 208 525 -8377 Fax (208) 55— 381 3 —D P.O. Box 50845 Idaho Falls, Idaho 83405 -0845 Total 1154- 205 -05.dw Contract Name: The Village Apartments Rexburg, Idaho Buildina 9 Contract with: Rocky Mountain Construction 560 West 1 st North Rigby, Idaho 83442 Description: Fire Protection Plan Scale: As Noted Drawn: C. Henscheid Checked: L. Hayward Date: 05/25/05 Revision: Contract # 1154 -205 Drawing: F -5 of 13 THIRD LEVEL FIRE PROTECTION PLAN SCALE: 1/8" = 1' -0 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 A B c D F G H J K L IL EPT 'TION BELL FITTERS NOTES 0 P 1) ALL CPVC PLASTIC PIPE DIMENSIONS SHOWN ARE CENTER TO CENTER OR CENTER TO END. DIMENSIONS SHOWN FOR THREADED PIPE IS CUT LENGTH. 2) WHERE FIRE SPRINKLER PIPING PENETRATES IDENTIFIED FIRE WALLS, FIRE CAULK AND SEAL PENETRATIONS AS REQUIRED. 3) COORDINATE THE LOCATION OF ALL SPRINKLER PIPING WITH OTHER SUBCONTRACTORS ON THE JOB TO AVOID POSSIBLE OBSTRUCTIONS TO SPRINKLER DISCHARGE. E APPROVAL STAMP R T NOTICE IT IS THE OWNER'S RESPONSIBILITY TO PROVIDE ADEQUATE HEAT TO PREVENT FREEZING THROUGHOUT WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS. WATER SUPPLY INFORMATION STATIC 90 Psi RESIDUAL 85 psi GPM FLOWING 1252 FLOW DATE 09/05/03 LOCATION _Pioneer Road SOURCE OF INFORMATION 3 —D Fire Protection Inc. Waterflow Test THIRD LEVEL FIRE PROTECTION PLAIN CONTROL VALVE — — — — — — — NOMENCLATURE KEY VALVE --- - - - - -- CROSS MAIN DESIGNATION---- I CRQSSMAIN n° ALARM VALVE & RISER — — — — — �-- FEED MAIN DESIGNATION— — — — — — — FM ^° HORIZONTAL ALARM VALVE — — — — — ELEVATION TO CL' OF PIPE (AS NOTED) — — F DRY PIPE VALVE & RISER — — — — ®— LINE DESIGNATION — — — — — — — — — 0 DELUGE VALVE & RISER — — — — �— CALCULATION DESIGNATION — — — — — — O CHECK VALVE — — — — — — — — -t�- NEW UNDERGROUND — — — — — — — — - m - _ - m - mi — FLOW SWITCH — — — — — — — — O-V EXISTING UNDERGROUND — — — — — — WATER MOTOR GONG — — — — — REVISIONS — — — — — — — — — — — — — ELECTRIC BELL - - - - - -- 155' CONTROL VALVE — — — — — — — --p�<— KEY VALVE --- - - - - -- —�— POST INDICATOR VALVE (PIV) — — — — p�}— PIV W /TAMPER SWITCH — — — — — —— FIRE DEPARTMENT CONNECTION — — V STANDARD PENDENT SIDEWALL — — FLUSH FIRE DEPT CONNECTION — — " FIRE HYDRANT — — — — — — — — c --o—� FIRE HYDRANT W /PUMP DRY PENDENT HEAD — — — — — UPRIGHT ON 1" RISER------- —Q— STANDARD UPRIGHT HEAD — — — — — — __0_ STANDARD PENDENT HEAD — — — — — — PENDENT HEAD BELOW CEILING — — — — —— STANDARD UPRIGHT SIDEWALL -- — — — -- a4 STANDARD PENDENT SIDEWALL — — — — --�4 HORIZONTAL SIDEWALL — — — — — — — —� HEAD ABOVE & BELOW CEILING — — — — DRY PENDENT HEAD — — — — — — — FLUSH TYPE HEAD — — — — — — — —— EARTHQUAKE BRACE White RISE UP ----- - - - - -- —o— DROP DOWN---- - - - - -- a INSTALLATION /LAYOUT DRAWINGS INDICATE THE PROPOSED LOCATION OF PIPING, PIPE STANDS, COMPONENTS, ETC. FIELD ADJUSTMENTS OF PIPE ROUTING, PIPE LENGTHS, AND POSITIONING OF HANGERS, ETC. SHALL BE ANTICIPATED AND EXPECTED. THESE CHANGES SHALL MEET NFPA REQUIREMENTS AND ARE TO BE RED —LINED AND INCORPORATED ONTO THE "AS— BUILT" DRAWINGS ACCORDINGLY. HANGERS 1. All— thread rod A. Top Beam Clamp 2. U —hook B. Nut & Washer 3. Coach screw C. Unistrut Nut 4. Eye —rod D. Drop —in Anchor 5. U —bolt E. Hilti Stud 6. Pipe strap F. Lag Bolt 7. Bracket G. Rod Coupling B. H. Wing Toggle 9. Special (See Detail) I. Side Beam Bracket Tyco Series LAI J. Speedy Fastener 4) LOCAL AUTHORITY HAVING JURISDICTION: REXBURG FIRE CHIEF CHRIS HUSKINSON— TELEPHONE: 359 -3010 CAROL HENSCHEID NICEf III NO. 100827 ENGINEERING TECH. 2005 ^ T AN LANS iwT�� %Lfl — — CHAa��x TION IS L •, ::, ; RlwulE�qEr.? z�'r __ - — _ 0 5' 10' 20' ffj ffmm SCALE: 1/8" = 1' -0 Contract Name: The Village Apartments Rexburg, Idaho Buildina 10 Contract with: Rocky Mountain Construction 560 West 1 st North Rigby, Idaho 83442 Description: Fire Protection Plan Scale: As Noted Drawn: HEAD COUNT L. Hayward Date: 05/25/05 Revision: 3 FIRE PROTECTION, INC. Design • Installation Maintenance • Inspection 3\ For Service or Repair D & 24 Hrs. Emer ency Service Please Call (208 525- 8377 Fox (208) 525— 381 3 —D P.O. Box 50845 Idaho Falls, Idaho 83405 -0845 Sprinkler Type Fin. Orif. K —Fac. Can Temp. Symb. Qty. Tyco Series LAI SW White - -- 4.2 White 155' Q 39 Tyco Series LFII Pendent White - -- 4.9 White 155' @ 7 3 Tyco Series TY —FRB Upright Brass 1/2" 5.6 - -- 155' 0 1 Total 113 1154- 205 -06.dw Contract Name: The Village Apartments Rexburg, Idaho Buildina 10 Contract with: Rocky Mountain Construction 560 West 1 st North Rigby, Idaho 83442 Description: Fire Protection Plan Scale: As Noted Drawn: C. Henscheid Checked: L. Hayward Date: 05/25/05 Revision: Contract # 1154 -205 Drawing: F -6 of 13 FIRST LEVEL FIRE PROTECTION PLAN SCALE: 1/8" = V -0 SECOND LEVEL FIRE PROT PLAN SCALE: 1/8" = V-0 —0