HomeMy WebLinkAboutDOCS - 07-00244 - Legacy Network - Site PlanBuilding Safety Department
City of Rexburg
19 E. Main janellh@rexburg.org Phone: 208.359.3020
Rexburg, ID 83440 www.rexburg.org Fax: 208.359.3024
. pEX6 UqC �7
U � �
CITY O F
MXIi
America's Family Communiq
Site Plan Checklist
Permit Number:
Application Information
Applicant: Randy Webb Phone: 208- 529 -3436 FAX: 208- 523 -2958
Applicant's Address: 567 W. 19th City: Idaho Fal l sST: ID Zip: 83402
Project Address: I WK A c-> P� IQ -* 9- Ch V) (C - ;�Gpu o
Recorded Owner: Randy Webb
Recorded Owner Address: 567 W. 19th
Development Information
Phone ? 08 - 529 - 3436 FAX :2 08- 523 -2958
City:I Fal l s ST: ID ZipB 3402
■ 1. Site plan must be drawn to scale, be legible and also be submitted electronically if possible.
■ 2. Adjoining streets labeled.
i 3. Right - of - way location and width, curb to curb widths and sidewalk location.
■ 4. Building location, sq footage and dimensions, with distance to property lines and distances
between buildings.
■ 5. Show existing and proposed easements.
■ 6. Existing utilities (waterlines, sanitary sewer lines, manholes, storm drains).
■ 7. Proposed utilities including tie in location to existing services and new easements.
■ 8. Proposed storm drain and sanitary sewer elevations (for pipe inverts at manholes and catch basins).
® 9. Storm drainage plan for parking lot and roof areas, with calculations. — FEN 1-54. Sys�EN1.
■ 10. Fire hydrants and fire suppression lines (including tie to City lines).
❑ Sprinkled ® Not Sprinkled
■ 11. Indicate Fire apparatus access.
■ 12. Parking (including parking lot, drainage arrows, dimension of lot, distance between rows, and total
numbers).
■ 13. Landscaping (type and total area, including dimensions).
1014. Trash facilities. 0 nn
■ 15. North Arrow U
■ 16. Drawing to Scale, including a graphic scale (11 %2 x 17" paper if po ).
® 17. Proposed street improvements (curb, gutter, sidewalk, pavement, et MAY Q 2007
■ 18. Legal description of proposed building site included.
■ 19. Percent of lot covered by building or paving calculated. C ITY O F R EXB U R G
20. Show 10% snow storage area.
■ 21. Distance of entrances from street corner indicated.
■ 22. Current Vicinity Map. (81/2 x 11 ") at 1" = 300' scale, showing location of the property.
■ 23. Lighting Plan
NOTE: SITE PLANS MUST BE COMPLETE AND SUBMITTED FOR REVIEW BEFORE THE PROJECT WILL BE
PLACED ON THE PLANNING & ZONING AGENDA. -'E'
0
FoP,-,.S
August 3, 2007
Mr. Randy Webb
567 West 19
Idaho Falls, ID 83402
0
RE: Fire Flow Testing for Webb Custom Homes in Rexburg Idaho
Dear Mr. Webb:
We completed the flow testing at the north east comer lot of the Valley Wide Coop Subdivision on
August 2, 2007. We used the three hydrants nearest the lot to measure system static and residual
pressures. Two hydrants were opened for flow metering. Hydrant 1 was the nearest hydrant west of
the lot and Hydrant 2 was just south of the lot. Hydrant 3 was adjacent to the parking lot for the
Evans Hairstyling building.
We measured flows as summarized below-
Test
Flow
System
Est.
Est. Syst.
Notes .
Number
Pressure
now
Pressure
(-.Pm)
(psi)
m
(psi)
1
1292
57
2084
20
Measured at Hydrant 1
2
1119
57
1805
20
Measured at Hydrant 2
3
769
30
844
20
Measured at Hydrant 2 with Hydrant 1 open -
4
813
30
892
20
Measured at Hydrant 1 with Hydrant 2 open
Maximum measured flow was 1292 gpm for a single hydrant and 1582 gpm with two hydrants open.
Static pressure before testing was 83 psi and dropped to 30 psi with two hydrants open. Using a
modified Hazen Williams equation calculation recommended by the manufacturer of our flow meter,
maximum flow rate from a single hydrant is 2084 gpm at a minimum system pressure of 20psi.
The calculated maxim flow rate at 20 psi system pressure was less than the rate for a single
hydrant. Available flow in a water system can vary widely throughout the day and year based on
system use. Under the instantaneous flow conditions at the precise time the test was conducted, it
was not possible to achieve greater then 2084 gpm and maintain the required minim system
pressure of 20 psi.
If you have any questions, please contact me at (208) 356 - 9201.