SITE PLAN REVIEW
City of Rexburg
Department of Community Development
19 E. Main St. / Rexburg, ID. 83440
Phone (208) 359-3020 /Fax (208) 359-3022
Project Information Permit # OS 00007
Permit Type Site Plan Review Project Name Romney Bldg Add
Site Address Parcel # RP06N39E207351
Project Description
Romney Bldg Add
Names Associated with this Project
Type Name Contact Phone # License # Exp Date
Applicant Byui
Fee Information
Project Valuation
Site Review Fee 680.00
Base Fire Fee 50.00
Total Fees Paid $730.00
Print Name Date Issued:
Signature Date Issued By:
~eHr.,Y~Q,.~-,
~~
a ~+
~4ec+s~~o°#
8/19/2005
Cl 1 1 ~.J~
R~cBUR~
AMERICA'S FAMILY COMMUNITY
Lloyd Benson
BYU Idaho Physical plant
Rexburg, ID 83440
~9 fast Ma1n St. 208-3593020 Phone ext.32~
Po Box 280 208-359,3024 Fax brad~C~ci.rexbur~.id.us
Rexburg, Idaho 83440 www.rexbur~.org
0n August 18, 2005 during the fire inspection on the Romney building the following violations were
noted. NFPA 45 requires an emergency gas shut off valve outside of each laboratory. These valves are
required to be installed before the gas system for the laboratory will be used. There are. two interior stair wells
with doors that are required to have panic hardware installed before occupancy will be given. Please repair
exit signs and maintain them. The alarm system does not have outside notification with water flow.
All of the existing fire system components are required to be removed if they are not part of the fire
system. This will include old fire alarm panels and hose cabinets. There are shelves in room # 12dA & # 15 0
that are too close to the fire sprinklers. The shelves are required to be lowered or the fire sprinkler heads are to
be relocated. All of the mechanical rooms have penetrations that are required to be sealed. This will need to
have a dust collection system installed. I am still waiting for the information requested on the fume hoods so
the fire department can class the hood systems. Information should include chemicals with quantities and the
mechanical information on the hoods. In addition you will be required to submit a Hazardous Material
Management Plan and a Hazardous Material Inventory Statement as outlined in Chapter 27 Section 2701.5 of
the International Fire Code.
The fire department would also like to notify you about the fire apparatus access. There is no access
to the Romney and other buildings due to construction and college vehicles blocking access roads. The fire
department would like you to address this serious situation. This is considered to be a life safety issue. All life
safety violations are addressed in the City of Rexburg ordinances and the 2003 International Fire Code.
Before any access that is blocked or out of service requires you to notify the fire department.
Sincerely,